INSTRUCTIONS FOR USE AND MAINTENANCE
4.4. The storage cooling method
Pre-work cooling procedure
1. To start you must have a minimum of 0.5kg of
liquid refrigerant in the tank.
2. Turn the Recover/Purge valve to the Recover
position.
3. Open the Vapor and Liquid valve of the storage
tank.
4. Power on, and start the compressor.
5. Open the Input valve and Output valve of the
unit.
Filter
Vapor
Liquid
Recovery
tank

5. Troubleshooting

PROBLEM
Fan does not run
when power Switch is
in "ON" position
Fan
runs
but
compressor does not
start when the Start
Switch is in "ON"
position
Compressor starts but
cuts off within a few
minutes
Recovery process too
slow
Unit does not pull out
a vacuum
Input
Refrigerant
recovery
machine
Output
CAUSE
Power supply cord not attached Voltage
is not right
The circuit breaker has cut off
The unit is in high pressure shut off
Output pressure is too high
Failure in motor, or other electrical
components
Purge valve is in "PURGE" position
Output valve is not open and high pressure
activates
Recovery tank valve is not open
Head pressure too high
Compressor seals are worn
Connecting hoses are loose
Leakage in unit
20
6. Throttle the Output valve of the unit so that the
output pressure is 100psi greater than the input
pressure, but never more than 300psi.
7. Run until tank is cold
4.5. Tank Cooling Procedure in the recovering process
1. Open the vapor valve of the storage tank (it is
closed while recovering).
2. Close the two valves of the manifold gauge set.
3. Follow the sixth and seventh items of the
Pre-work Cooling Procedure.
Manifold
gauge set
HVAC System
Vapor
Liquid
A scale must be used to avoid
overfilling the recovery tank
Attach the power supply cord.
Check the power supply at job site.
Press the button to reset.
Reduce pressure and then press the
button of the High Pressure Switch.
Rotate Input valve to "CLOSE", Purge
valve to "PURGE", then rotate Input
valve back to "OPEN", Purge valve to
"RECOVER".
Factory service required
Rotate Purge valve to "RECOVER"
Rotate Output valve to "OPEN"
Open recovery tank valve
Reduce tank temperature with
Storage Tank Cooling Method
Factory service required
Tighten the connecting hoses
Factory service required
Input
Refrigerant
Filter
recovery
Output
tank
Vapor
Liquid
Recovery tank
ACTION