Installation procedure
a): Normal mounting
4.8 mm dia. holes
Rawl plug
6
b): Flush mounting
1. Decide how the system controller will be mounted: in the normal manner
or fl ush with the wall.
a) To mount the system controller in the normal manner, remove the
mounting plate. Then reattach the four screws to the electrical
component box.
b) To mount the system controller fl ush with the wall, make an opening in
the wall measuring 128 mm × 128 mm. The opening must be at least
85 mm deep as measured from the outside surface of the wall.
2. Remove the rear plate and connect the electrical wiring.
1) Remove the four screws located on both sides of the rear plate.
2) Either the hole in the bottom of the electrical component box or the
hole in the rear plate may be used to feed the electrical wiring.
3. Secure the system controller in place.
a) If the system controller is being mounted in the normal manner, fi rst
attach the rear plate to the wall using the screws and Rawl plugs
provided. Next, place the body of the system controller over the rear
plate and secure it in place using four screws.
b) If the system controller is being mounted fl ush with the wall, fi t it
through the mounting plate on the wall and secure it in place using the
screws and Rawl plugs provided.
To mount the system controller on a wall made of cinder block,
NOTE
brick, concrete, or a similar material, drill 4.8 mm diameter holes
in the wall and insert Rawl plugs to anchor the mounting screws.
Mounting plate
Electrical
component box
Rear plate
Hole for electrical
wiring
Fig. 2