4.u - ALARM MEMORY AND CLEAR ALARM MEMORY
The appliance memorizes when an alarm has been triggered, and also at the return
to normal conditions in the environment, the user can check whether or not there has
been an alarm in the environment (the 3 red LEDS blinking) (fig. 9).
To clear the alarm memory, press the "
"normal operation" status (fig. 3).
Fig. 9 - Alarm memory
EN
Green LED - alight
!
Yellow LED - off
Red LED 1 - blinking
Red LED 2 - blinking
Red LED 3 - blinking
Buzzer - off
Relay - activated
(Solenoid valve closed)
CAUTION! IN CASE OF ALARM
• EXTINGUISH ALL THE FLAMES AND SMOKING MATERIALS.
• EXTINGUISH ALL THE GAS POWERED DEVICES.
• SHUT OFF THE GAS SUPPLY AT THE METER OR CLOSE THE VALVE OF
THE LPG CYLINDER.
• DO NOT OPERATE LIGHT SWITCHES (ON OR OFF); DO NOT SWITCH ON
ELECTRICAL APPLIANCES AND DEVICES.
• DO NOT USE THE PHONE IN PRESENCE OF GAS LEAKAGE.
• OPEN DOORS AND WINDOWS TO INCREASE VENTILATION IN THE
ENVIRONMENT.
If the alarm stops, find out the cause and take the appropriate corrective
action.
If the alarm continues and the gas escape cannot be located or eliminated,
leave the building and call the emergency services from outside.
16
RESET
" button and the appliance will return to
BUS connection only
W h e r e s e v e r a l u n i t s a r e B U S
connected, activation of the alarm
memory in a peripheral unit is signalled
at the main unit by the red LED 1 only,
which blinks.
The alarm memory clearing is done by
pressing the "
RESET
" button of the
peripheral unit from which the alarm
was generated; the memory will be
cleared automatically at the main unit.
5.u - PERIODIC INDICATIONS
Periodic appliance replacement warning
(after 5 years of operation)
The appliance automatically warns when it is time for replacement in accordance with
regulations (after 5 years of operation): the green LED, yellow LED and red LED 1 will
flash simultaneously and a dual acoustic signal will sound every hour.
Temporary deactivation of the appliance replacement warning signal
The signal can be deactivated by pressing "
automatically reactivated.
RESET
Resetting the appliance replacement signal
With the appliance replacement signal active (green LED, yellow LED, and red LED 1
flashing) it is possible to reset the operating hours counter. Press and hold down the
"
RESET
" button until red LED 1 switches off, then release the button. The appliance
switches to "normal operation" mode (chap. 1.u - fig.3) and the counter restarts the
operating hours count for a further period of 5 years.
"Gas presence" and " Gas presence alarm" signals with the appliance
replacement signal active
All gas presence signals (with the exception of the "Gas presence alarm") and the
alarms event memory are superimposed over the appliance replacement signal.
-
6.u FAULTS INDICATION
Fig. 10 - Indication of breakdowns
and faults
Green LED
Yellow LED
Red LED 1
Red LED 2
Red LED 3
Buzzer
permanently on
off
intermittent
Warning: when "breakdown or fault" is indicated, call the installer.
RESET
"; after one month the signal will be
1 month
When the yellow Led is permanently
alight or the buzzer rings continuosly,
these indicate a breakdown or fault
detected by the self-diagnostic system
of the appliance (fig. 10).
BUS connection only
Where a detector functions as main unit
in a BUS connection, the yellow Led
permanently alight indicates a
breakdown or wrong connection of the
BUS line, or the incorrect operation of a
peripheral unit connected to the bus.