Accessories

Fastening set

For the assembly of LFC and IC. The fastening set
is fitted at the factory or delivered enclosed as an
additional item.
Fastening set
IC-BVG/BVA/BVH/LFC /B (enclosed)

Flange set for Moduline

For attaching solenoid valves for gas VAS 1/
VAS 2 or double solenoid valves VCS 1/VCS 2 to
LFC 1/LFC 2:
Flange set
VA1/LFC 1
VA2/LFC 2
VA1/LFC 1
60
1
2
3
1
1 x flange LFC 1/LFC 2
1 x O-ring
3
4 x set screws M5 x 16

Maintenance

In order to ensure smooth operation:
For operation with natural gas, town gas and
LPG, check the function annually.
For operation with biologically produced methane,
service every half year.
After carrying out the maintenance work, check
for tightness.

Contact

If you have any technical questions, please contact
your local branch office/agent. The addresses are
available on the Internet or from Elster GmbH.
We reserve the right to make technical modifications
in the interests of progress.
Order No.
74921082
Order No.
74922171
74922172
VA2/LFC 2
50
1
3
2

Technical data

Gas type: natural gas, town gas, LPG and air.
Control ratio: 25:1.
Leakage rate: < 2% of k
Max. inlet pressure p
Running times: 7.5 s, 15 s, 30 s, 60 s.
Connection flanges: Rp internal thread pursuant
to ISO 7-1.
Housing material: aluminium, control cylinder:
POM.
Ambient temperature: -20 to +60°C.
Installation position: any.

Declaration of conformity

We, the manufacturer, hereby declare that the product
LFC, marked with product ID No. CE-0085AP0254,
complies with the requirements of the listed Direc-
tives and Standards.
Directives:
90/396/EEC
2006/95/EC
2004/108/EC
Standards:
EN 161
The relevant product corresponds to the type tested
by the notified body 0085.
The production is subject to the surveillance pro-
cedure pursuant to DIN EN ISO 9001 according to
annex II, paragraph 3 of Directive 90/396/EEC.
Elster GmbH
Scan of the Declaration of conformity (D, GB) – see
www.docuthek.com
Elster GmbH
Postfach 28 09, D-49018 Osnabrück
Strotheweg 1, D-49504 Lotte (Büren)
T +49 541 1214-0
F +49 541 1214-370
info@kromschroeder.com, www.kromschroeder.com
8
value.
VS
: 500 mbar.
e max.

Publicidad

Tabla de contenido
loading

Tabla de contenido