PM 3 Setting Instructions (INCOM)
8a
1
1. Communications & Auxiliary Power
}
1.1. Incom
1.2. Incom
1.3. Shield
1.4. N/C
1.5. Power Supply Positive - 24VDC
1.6. Power Supply Common
(Auxiliary Power is NOT Hot Swappable. Power should be turned off prior to connector installation)
2. Breaker Aux/Bell Attachment & Neutral Voltage
2.1. Breaker Bell Alarm Normally Closed Contact
2.2. Breaker Bell Alarm Common Contact
2.3. Breaker Auxiliary Switch Common Contact
2.4. Breaker Auxiliary Switch Normally Closed Contact
2.5. Neutral Voltage (optional)
3. Network Address - This sets the INCOM Network Address. Range is 0 (0x01 hex) to 255 (0xFF hex).
4. Settings
4.1. Reverse Power - If the unit is reporting negative power, this switch can be toggled so that it reports posi
tive power. This will also change the orientation of the Energy readings. For example, Forward Energy will
become Reverse Energy. This is usually an indication of the PM3 being reverse fed.
4.2. Phase Rotation - The PM3 is set so that the left pole of the unit is designated as Phase A,
the center pole as Phase B, and the right pole as Phase C. Depending on the application or orientation of the
PM3, it may be necessary to change the designation so that the left pole is designated as Phase C, and the
right pole as Phase A.
4.3. Nothing
4.4. Nothing
6
Communications Connections
}
Auxiliary Power Connections
EATON CORPORATION www.eaton.com
4
*NOTE: Image shown is LG/KD PM3; con-
nection points and switches same on FD and
3
JG PM3.
}
These connections determine the breaker status.
If not installed the PM3 will report Unknown Status.
2