System Test - Detnov CAD-150-R Manual Del Instalador

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

The basic configuration of the repeater can be made entirely from the keypad of the
repeater but it is recommended to use the configuration software provided as the process
will be simpler and faster. To gain access to the configuration menu you should unlock
the system by introducing the key 2222. Follow the next step for a quick start.
GB
Select the Language. By default, the language of the repeater is configured in Spanish.
Access the GENERAL menu where, under the IDIOMA submenu, there you can select
your language.
Date and Time Settings. To set the date and time enter the DATE-TIME submenu.
Name the installation. To set the installation and maintenance company info access
the GENERAL menu and then the INSTALLATION NAME submenu.
 C onfigureanode. Enter the NETWORK menu and then open the CONFIGURE NODE
submenu. Set the type node as NORMAL and assign a free node id in the ADDRESS
submenu.
Once all the steps outlined above have been carried out, the system is configured to
protect the installation.
A quick test of the system can be performed as follows:
Create a fault, such as a loop open circuit or a power failure, and check that the fault
relay operates and the fault is indicated on the Indicadors and LCD.
Cause an alarm to occur and check that the alarm relay outputs are activated and the
correct sounders operate (after the correct delay, if programmed).
Note: A power failure may take several minutes to be indicated.
3.3 - A Basic Configuration Installation

3.4 - System Test