User Configurable Items
UPS Settings
Settings are adjusted through PowerChute
Function
Automatic
Self-Test
UPS ID
Date of Last Battery
Replacement
Minimum Capacity Before
Return from Shutdown
Voltage Sensitivity
Alarm Delay Control
Shutdown Delay
Storage
Store the UPS covered in a cool, dry location with the batteries fully charged.
At 5° to 86° F (–15° to 30° C), charge the UPS battery every six months.
At 86° to 113° F (30° to 45° C), charge the UPS battery every three months.
Installing/Replacing the Battery Module
This UPS has an easy-to-replace, hot-swappable battery module. Replacement is a safe procedure, isolated from electrical hazards. You
may leave the UPS and connected equipment on during the replacement procedure.
Troubleshooting
Access the troubleshooting guide for this UPS through PowerChute software.
Allen-Bradley Company, LLC
Industrial Components Business
1201 South Second Street
Milwaukee, WI 53204-2496 USA
Phone 440.646.5800
www.ab.com
41063-214-01 (1)
software.
Factory Default
User Selectable Choices
Every 14 days (336
• Every 7 days
hours)
(168 hours)
• On start up only
• No self-test
UPS_IDEN
Up to eight characters
(alphanumeric)
Manufacture Date
mm/dd/yy
0 percent
• 0%
• 15%
• 30%
• 45%
High sensitivity
High sensitivity
Medium sensitivity
Low sensitivity
Enable
• Enable
• Mute
• Disable
90 seconds
• 0 s
• 90 s
• 180 s
• 270 s
Set the interval at which the UPS will execute a self-test.
Uniquely identify the UPS (i.e. server name or location) for
network management purposes.
Reset this date when you replace the battery module.
• 60%
Specify the percentage to which batteries will be charged
following a low battery shutdown before powering connected
• 75%
equipment.
• 90%
The UPS detects and reacts to line voltage distortions by
transferring to battery operation to protect the connected
equipment.
In situations of poor power quality, the UPS may frequently
transfer to battery operation. If the connected equipment can
operate normally under such conditions, reduce the
sensitivity setting to conserve battery capacity and service
life.
Mute ongoing alarms or disable all alarms permanently.
• 360 s
Set the interval between the time when the UPS receives a
shutdown command and actual shutdown.
• 450 s
• 540 s
• 630 s
Description