Bosch FCS‑320‑TP Serie Guía De Instalación Rápida página 18

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 22
18
en | Connection
Sensitivity
DM-TP-01(05)
DM-TT-01(05)
(0.4%/m)
0.06%/m
(0.2%/m)
0.03%/m
(0.1%/m)
0.015%/m
(0.05%/m)
Alarm delay
0 seconds
10 seconds
30 seconds
60 seconds
Activation threshold for airflow malfunction
Low (+/- 10% volume flow change)
Average (+/- 20% volume flow change)
High (+/- 30% volume flow change)
Very high (+/- 50% volume flow change)
Airflow fault delay
30 seconds
2 minutes
15 minutes
60 minutes
Trouble logging
not saving
saving
Notice!
The sensitivity value is based on measurements with standard test fires (old value in
brackets).
The activation threshold for the airflow malfunction is set to 20% volume flow change by
default. Higher values are not permitted within EN 54‑20 or ISO 7240-20 .
2020.04 | 3 | F.01U.130.927
DM-TP10(25)
DM-TP50(80)
DM-TT-10(25)
DM-TT-50(80)
(2%/m)
0.4%/m
-
(1%/m)
0.2%/m
1.0%/m
(0.5%/m)
(1.6%/m)
0.1%/m
0.5%/m
(0.25%/m)
(0.8%/m)
DIP settings
Switch 9
off
on
Quick installation guide
Conventional aspiration smoke detector
DIP settings
Switch 1
off
on
off
DIP settings
Switch 3
off
on
off
on
DIP settings
Switch 5
on
off
off
on
DIP settings
Switch 7
off
on
on
off
LOGIC·SENS filter
off
on
Bosch Sicherheitssysteme GmbH
Switch 2
on
off
off
Switch 4
off
off
on
on
Switch 6
off
on
off
on
Switch 8
on
off
on
off
DIP settings
Switch 10
off
on

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Fcs-320-tp1Fcs-320-tp2

Tabla de contenido