6- INSTALLAZIONE
MCBT80
Depending on the various types of installation, the actuators can be driven by the
following control devices:
1)MANUAL PUSH-BUTTON:
Two-pole push-button switch with central OFF position and "dead man" control.
2)CONTROL AND POWER UNIT :
Microprocessor control units (e.g.: Mod. TF, EVP, etc.) controlling a single actuator or
several actuators simultaneously by means of one or more manual push-buttons, an
infrared remote control or a 433 MHz radio control.
Rain sensors (RPR - 12V), the wind sensor (RW) and the brightness sensor (RL) can
be connected to these control units.
6.6-
EMERGENCY PROCEDURES
Should it be necessary to open the window manually due to a blackout or mechanism
failure, follow these instructions:
BEFORE WORKING ON THE ACTUATOR AND WINDOW, DISCONNECT THE ACTUATOR
FROM THE POWER SUPPLY AND SET ANY CONTROL DEVICE SWITCHES TO "0" .
PADLOCK THE MAIN SWITCH OF THE SECTIONING DEVICE INSTALLED ON THE MAINS
LINE TO PREVENT ACCIDENTAL START-UPS. IF THE MAIN SWITCH CANNOT BE
PADLOCKED, PLACE A SIGN FORBIDDING OTHER PEOPLE FROM STARTING THE
DEVICE.
6.6.1- Single actuator
1) Fig. 13 page 107 - Unscrew the "D1" nut and remove the "V2" screw from the "SF"
butterfly bracket;
2) Open the window by hand.
6.6.2- Pair of actuators
1) Fig. 24 page 110 - Unscrew the "D4" nut and remove the "V6" screw from the "SF"
butterfly bracket;
2) Open the window by hand.
VER.1.0
REV.08.06
INSTALLATION AND USE INSTRUCTIONS
INSTALLATION -6
EN
39