Installation Instructions
Installation Instructions
Please Read Before Installing
Please Read Before Installing
Overview
The 4 Series Processors, model numbers H4P5-H48-
120, H4P5-H48-HRL-120, H4P5-120, and H4P5-HRL-
120, have three (3) configurable communication links
allowing connection of HomeWorks Wired Keypads,
HomeWorks Wired Maestro
HomeWorks Wallbox Power Modules, and SOLos
Homeworks/Sivoia QED
Integrators. Model numbers
TM
H4P5-H48-HRL-120 and H4P5-HRL-120 have an
additional dedicated link for Hybrid Repeaters, allowing
expansion to RF devices. The central processor provides
lighting presets, astronomic timeclock events, security
mode, vacation mode, conditional logic, and all other
HomeWorks programming functions.
A maximum of 10 seeTouch
150 LEDs) may be powered by Link 6 on the 4 Series
Processor. To power additional keypads, or to use
keypads on Links 4 or 5, an additional power supply is
required (Lutron model # T120-15DC-9-BL).
The dedicated Hybrid Repeater Link (Link 8) on H4P5-
H48-HRL-120 and H4P5-HRL-120 processors can provide
power to Hybrid Repeaters. Each Hybrid Repeater counts
as 30 LEDs towards the maximum of 150 LEDs.
Important Notes
Codes: Install in accordance with all local and
national electrical codes.
Power: Two separate power inputs exist on this
processor:
1. Processor power is provided by the 2 conductor
harness that is integral to the HWI-LV24 enclo-
sure. The processor is powered when the green
LED labeled "PWR" is on.
2. Keypads connected to Link 6 are powered by the
supplied plug-in adapter connected to the power
jack labeled "Link 6 15 V
properly when the green "LINK PWR" LED is on.
If the red "LINK SHORT" LED is on, Link 6 or 8 is
shorted (between terminals 1 and 2) or
overloaded (exceeding 150 LEDs).
Both Processor power and Link 6 and 8 power must
be present for the processor and keypads to function
properly.
Local Lighting Controls,
®
TM
keypads (equivalent to
TM
". Link 6 is powered
4 Series
Processor
TM
H4P5-H48-120, H4P5-H48-HRL-120
H4P5-120, H4P5-HRL-120
12 V
60 Hz 30 W
H4P5-H48-120 H4P5-H48-HRL-120
Plug-in Adapter
T120-15DC-9-BL
Input: 120 V
60 Hz 19 W
Output: 15 V
900 mA
NEC Class 2; IEC PELV
Figure 1 - 4 Series Processors and Adapter
Processor Power: 12 V
Link 6 and 8 Power: 15 V
NEC Class 2; IEC PELV
Use only the adapter provided by Lutron with
the 4 Series Processor (Lutron model # T120-
15DC-9-BL).
Environment: Ambient operating temperature:
0-40°C, 32-104°F, 0-90% humidity, non-condensing.
Indoor use only.
Cleaning: To clean, wipe with a clean damp cloth. DO
NOT use any chemical cleaning solutions.
H4P5-120
H4P5-HRL-120
30 W
900 mA
1