ELECTRICAL CONNECTION INSTRUCTIONS
Step 1. Provide electrical service according
to your local electrical code to the wiring box
located on the plaster frame. Supply wire
insulation must be rated for at least 90˚C.
Step 2. Remove wiring box cover. Remove
the appropriate round knock-out(s) and
accommodate the type of electrical service to
be used/allowed by your local electrical code.
(Fig. 5)
Metal Conduit (rigid or flexible)/Non-Metallic
Sheathed Cable Remove appropriate round
knock-out(s) and connect conduit to wiring box
with proper connectors (not supplied).
EMERGENCY BATTERY BACK UP WITH REMOTE TEST SWITCH (BR OPTION)
When the fixture is ordered with the emergency battery back up
option (BR), the housing comes from the factory with the battery
pack already wired to the fixture and a carton with the test switch
accessories (shipped in same carton as housing).
Step 1. Provide electrical service according to your local electrical
code to the junction box located on the plaster ring. Supply wire
insulation must be rated for at least 90˚C.
Note: For proper charging and function of emergency battery,
an unswitched hot conductor must be connected to the battery
independant of the driver power.
Step 2. Remove wiring box cover. Remove the appropriate round
knock-out(s) and connect electrical supply to wiring box with proper
connectors (not supplied).
Step 3. Refer to the instruction manual provided by the battery
manufacturer located in the carton with the test accessories to
complete wiring and installation of emergency fixture and test switch.
DRIVER REPLACEMENT
Driver replacements must be performed by a qualified
electrician. Remove inner housing from fixture to access
driver. Order replacement kits as identified on the driver.
The replacement kits include detailed instructions for driver
replacement.
TRIM INSTALLATION
After ceiling is finished and painted, remove paint shield from
fixture. Discard or recycle. To install trims using COIL SPRINGS
remove OPTIC REFLECTOR by rotating 1/4 turn counter-
clockwise (Fig. 7). Connect trim springs to fixture L-BRACkETS
as shown (Fig. 8). Take note of flange details at top of OPTIC
REFLECTOR, align and insert in fixture and rotate 1/4 turn
clockwise until it stops.
To install trims with TORSION SPRINGS:
For lensed trims, it is not necessary to remove OPTIC
REFLECTOR. For lensed trims equipped with an internal reflector,
remove the reflector supplied with the trim and discard or recycle.
For hyperbolic trims, follow instructions provided with the trim.
1300 South Wolf Road • Des Plaines, IL 60018 • Phone 800-323-5068 • www.junolightinggroup.com
INSTALLATION INSTRUCTIONS
with Lutron Hi-Lume
Commercial Recessed Housing
Step 3. Strip supply wire 3/8" and insert
each supply wire into appropriate connector.
Connect black fixture wire to hot, white fixture
wire to neutral and green fixture wire to ground.
(Fig. 5)
For instruction on connecting dimmer wiring,
see page 3.
Step 4. Place all wiring and connectors back in
wiring box and replace cover.
FIXTURE
JUNCTION BOX
L-Bracket
TC920LED & TC922LED
Driver (-L Option)
®
Quick
Connector
WHITE
NEUTRAL
GREEN
GROUND
WHITE/RED
HOT SWITCHED FIXTURE POWER
HOT UNSWITCHED POWER FOR BATTERY CHARGING
ORANGE/BLACK
NOTES:
•
POWER FOR FIXTURE AND BATTERY CHARGING
MUST BE FROM THE SAME BRANCH CIRCUIT.
•
REFER TO THE EMERGENCY BATTERY
INSTRUCTIONS FOR ADDITIONAL WIRING
REQUIREMENTS.
Figure 6
Optic
Reflector
Figure 7
Coil
Spring
Figure 8
© 2014 Juno Lighting LLC
Knock-out
Figure 5
SUPPLY
CONNECTIONS
Rev 5/14
P3693
pg 2 of 4