T T e e s s t t l l o o a a d d f f o o r r s s h h o o r r t t c c i i r r c c u u i i t t s s
■
Turn power Off.
■
Connect standard switch between Hot/Live lead
and the load wire to test circuit.
■
Turn power On and check for short or open circuits.
Hot/Live
Neutral
I I n n s s t t a a l l l l a a t t i i o o n n I I n n s s t t r r u u c c t t i i o o n n s s
1 1 . . Turn power Off to the Control Unit.
2 2 . . Mount in provided 4x4 junction box (Lutron, P/N
241-496); 3 1/2 in. (89 mm) deep is strongly rec-
ommended, 2 3/4 in. (68 mm) minimum. Allow at
least 4 1/2 in. (110 mm) clearance above/below
Interfaces to ensure proper heat dissipation.
3 3 . . Strip 1/2 in. (12 mm) insulation from all wires in
wallbox and wire as shown. All connections are
made using #12 AWG to #16 AWG (2,5 - 1,0 mm
wire. Power terminals can accept up to two
#12 AWG (2,5 mm
installation torque is 9,0 in.
voltage connections.
Switch
Load
2
) wires. The recommended
lbs. (1,0 N
m) for line
●
●
1/2 in. (12 mm)
S S i i n n g g l l e e - - Z Z o o n n e e W W i i r r i i n n g g
Dimmer Circuit
Hot/Live
Neutral
(if necessary)
220 - 240 V
LUT-LBX-CE
Neutral
D D u u a a l l - - Z Z o o n n e e W W i i r r i i n n g g
Dimmer Circuit
Hot/Live
Neutral
(if necessary)
220 - 240 V
LUT-LBX-CE
2
)
Neutral
* Wallbox may be recess mounted or surface mounted.
If mounting Interface in a panel, please refer to Panel
Mounting section for important information.
3 3
Dimmed Hot/Live
LUT-LBX-CE
Dimmed Hot/Live, Zone 1
Dimmed Hot/Live
Zone 2
DIMMED HOT/LIVE
NEUTRAL
EARTH/GROUND
LUT-LBX-CE
Low-Wattage
Load
Low-Wattage
Load