LEGRAND Wattstopper FSP-212 Instrucciones De Instalación página 4

Sensor pir de voltaje de línea 0-10v para fixtruas y uso exterior
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Mode D – Indoor Parking Structure or High-Bay
Features: At dusk, turns ON with occupancy; High Dim Level sets Maximum ON level;
OFF at dawn
When the ambient lighting is below daylight control level and occupancy is detected, the load
turns ON at the level set with the Dim pot. Once no occupancy is detected and the time delay
expires, the load will turn OFF. Once ambient lighting rises to the daylight control level, the
load will turn OFF.
Mode E – Service Mode
Features: Allows visual adjustment of Dimming Level
If the Time pot is set at maximum, the load turns ON at the current Dim level. If the Time pot
is set at minimum, the load turns OFF.
Note that after turning the Time pot to change the ON/OFF setting, the unit will not respond to
further changes for 3 seconds.
Test Mode
Test mode sets the time delay to 5 seconds to allow for testing the occupancy sensor.
Whenever Mode C is selected using the Mode pot, the FSP-212 will enter Test mode for 5
minutes. If the FSP-212 is currently in mode C, selecting another mode and then returning to mode C will restart Test mode. During
Test mode, daylight control is not active and the value of the Time pot is overridden. When occupancy is detected the load will turn
ON at 10V. Once no occupancy is detected, the load will got to the dim level after 5 seconds, and then will stay at the dim level for 2.5
seconds, before turning OFF. After 5 minutes, the unit will revert to normal Mode C operation.
Daylight Control
Mode A*
Yes
Mode B
Yes
Mode C
No
Mode D
Yes
Mode E
No
* Default Mode Setting
Lights do not turn ON at Full Value:
• Make sure that the sensor is not obstructed.
• If Mode is set to A or B, check light level parameter, to find out the amount of light that the sensor is detecting. Cover the sensor
lens to simulate darkness in the room. If the lights come ON, the ambient light level is too high.
• If the red LED blinks 1 time per second, the FSP-212 is in short circuit protection mode.
• If the red LED blinks 2 times per second when the sensor is triggered, and in modes A, B, or D, the ambient light level is too high.
• Make sure the FSP-212 is not set to Mode E (Service mode) and time delay trim is not at minimum position.
• If lights still do not turn ON, call 800.879.8585 for technical support.
Lights will not go to Dimming Level:
• Check all wire connections and verify the dimming wires are tightly secured.
• Make sure that the sensor is not obstructed.
• If Mode is set to D, check light level parameter, to find out the amount of light that the sensor is detecting. Cover the sensor lens to
simulate darkness in the room. If the lights go the dim level, the ambient light level is too high.
• The time delay can be set from a minimum of 30 seconds to a maximum of 30 minutes. Ensure that the time delay is set to the
desired delay and that there is no movement within the sensor's view for that time period.
• To quickly test the unit operation, enable test mode and move out of the sensor's view. Lights should fade to the dim level after 5
seconds and then turn OFF after 2.5 seconds.
High/Low Dim
Low Dim
Default Level – Min. (1V)
Low Dim
Low Dim
High Dim
Low Dim
TROUBLESHOOTING
Time Delay
30sec – 30 min
Ambient light level below
daylight control level
Default – 15 min.
30sec – 30 min
Ambient light level below
daylight control level and
1/2 of set value
occupancy detected
during Low Trim
30sec – 30 min
Occupancy detected
1/2 of set value
during Low Trim
30sec – 30 min
Ambient light level below
daylight control level and
occupancy detected
Not applicable
Load is ON at Dim level
when time delay trim in
maximum position
4
Day
10
Dim
0
Occupancy
Applies Day or Night
10
Time Delay
set to maximum
Dim
0
3 seconds needed between changes
Auto On
Ambient light level above
daylight control level
One half time delay expired
or ambient light level above
daylight control level
One half time delay expired
Time delay expired or
ambient light level above
daylight control level
Load is OFF when time
delay trim in minimum
position
Mode D
Night
Day
Time Delay
Mode E
Time Delay
set to minimum
Auto Off

Publicidad

Tabla de contenido
loading

Tabla de contenido