3.5.2 Category 2 - System Settings

NOTE: To ensure correct heat pump system operation, parameter 8:Su must be set correctly. See note in
section 3.3 Using the Room Unit for Specific Applications.
Parameter
Parameter
No.
Category 2 Parameters – System Settings (press the
Heat/Cool selection
4:HC
enable / disable
Room Temperature
8:Su
Sensor Use
Maximum Flow
11:uF
Setpoint (extension
systems only)
Minimum Flow
12:LF
Setpoint (extension
systems only)
Mixing Value Run
13:Ar
Time (extension
systems only)
Pump Overrun Run
14:Pr
Time (extension
systems only)
Note
Remember to always press the green
setting. To exit the Installer Mode press the
Factory Default Setting
button to access this category)
0
Disabled
0
Programmer and
room compensation
unit
55
55°C Maximum Flow
Temp.
15
15°C Minimum Flow
Temp.
150
150 seconds
15
15 minutes
button to confirm that you want to store your new Installer Set-Up
or
button.
Optional Setting
1
Enabled
DO NOT CHANGE
1
Programmer only. Transmits demand
and room setpoint (no temperature
displayed)
0 to 99
0°C to 99°C adjustment in 1°C steps
0 to 50
0°C to 50°C adjustment in 1°C steps
0 to
0 to 240 sec. adjustment in 1sec
240
steps
0 to 99
0 to 99 mins adjustment in 1min steps