Lamborghini Caloreclima ERA F 23 Instrucciones De Uso, Instalación Y Mantenimiento página 6

Ocultar thumbs Ver también para ERA F 23:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Sliding Temperature
When the optional external probe is installed the boiler adjustment system works with
"Sliding Temperature". In this mode, the temperature of the heating system is controlled
according to the outside weather conditions to ensure high comfort and energy saving
throughout the year. In particular, as the outside temperature increases the system de-
livery temperature decreases according to a specific "compensation curve".
With Sliding Temperature adjustment, the temperature set with the heating buttons (de-
tails 3 and 4 - fig. 1) becomes the maximum system delivery temperature. It is advisable
to set a maximum value to permit system adjustment throughout its useful working
range.
The boiler must be adjusted at the time of installation by qualified personnel. Possible
adjustments can in any case be made by the user to improve comfort.
Compensation curve and curve offset
Press the button R (detail 6 - fig. 1) for 5 seconds to access the "Sliding temperature"
menu; the display shows "CU" flashing (fig. 11).
Operate the DHW buttons (details 1 and 2 - fig. 1) to adjust the curve from 1 to 10 ac-
cording to the characteristic (fig. 13). By setting the curve to 0, sliding temperature ad-
justment is disabled.
fig. 11 - Compensation curve
Press the heating buttons (details 3 and 4 - fig. 1) to access parallel curve offset; the
display shows "OF" flashing (fig. 12). Operate the DHW buttons (details 1 and 2 - fig. 1)
to adjust the parallel curve offset according to the characteristic (fig. 14).
fig. 12 - Parallel curve offset
Press the button
(detail 6 - fig. 1) again for 5 seconds to exit the "Sliding Tempera-
ture" menu.
6
EN
If the room temperature is lower than the required value, it is advisable to set a higher
order curve and vice versa. Proceed by increasing or decreasing in steps of one and
check the result in the room.
90
85
80
70
60
50
40
30
20
OFFSET = 20
90
85
80
70
60
50
40
30
20
fig. 14 - Example of compensation parallel curve offset
If the Remote Timer Control (optional) is connected to the boiler, the above ad-
A
justments are managed according to that given in table 1.
Table. 1
Heating temperature adjustment
DHW temperature adjustment
Summer/Winter changeover
Eco/Comfort selection
Sliding Temperature
Water system pressure adjustment
The filling pressure with system cold, read on the boiler water gauge, must be approx.
1.0 bar. If the system pressure falls to values below minimum, the boiler card will activate
fault F37 (fig. 15).
Once the system pressure is restored, the boiler will activate the 120-second
A
air venting cycle indicated on the display by FH.
cod. 3540L893 - Rev. 01 - 03/2018
ERA F 23 - 32 - 45 - 56
10
9
8
20
10
0
fig. 13 - Compensation curves
OFFSET = 40
90
10
9
8
7
85
6
80
5
70
4
60
3
50
2
40
1
30
20
Adjustment can be made from the Remote Timer Control menu
and the boiler control panel.
Adjustment can be made from the Remote Timer Control menu
and the boiler control panel.
Summer mode has priority over a possible Remote Timer Control
heating demand.
On disabling DHW from the Remote Timer Control menu, the
boiler selects the Economy mode. In this condition, the button N
(detail 7 - fig. 1) on the boiler panel is disabled.
On enabling DHW from the Remote Timer Control menu, the
boiler selects the Comfort mode. In this condition one of the two
modes can be selected with the button N (detail 7 - fig. 1).
Both the Remote Timer Control and the boiler card manage Slid-
ing Temperature adjustment: of the two, the boiler card Sliding
Temperature has priority.
fig. 15 - Low system pressure fault
7
6
5
4
3
2
1
-10
-20
10
9
8
7
6
5
4
3
2
1

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Era f 32Era f 45Era f 56

Tabla de contenido