Incandescent / 120 V Halogen Dimmer
RAY600 Series
Rated at 120 V~ 60 Hz 600 W
Important Notes
Please read before installing.
1. NOTICE: Use only with permanently-installed 120 V incandescent or halogen
fixtures. To avoid overheating and possible damage to other equipment, do not use
to control receptacles, fluorescent lighting fixtures, motor-driven appliances, or
transformer-supplied appliances.
2. Install in accordance with all national and local electrical codes.
3. When no "grounding means" exist within the wallbox then the NEC
404-9(B) allows a control without a grounding connection to be installed as a
replacement, as long as a plastic, noncombustible wallplate is used. For this type of
installation, cap or remove the green ground wire on the control and use an
appropriate wallplate.
4. For new installations, install a test switch before installing the dimmer.
5. Protect dimmer from dust and dirt when painting or spackling.
6. Only one dimmer can be used in a 3-way circuit.
7. Recommended minimum load is 40 W.
8. It is normal for the dimmer to feel warm to the touch during operation.
9. Clean dimmer with a soft damp cloth only. Do not use any chemical cleaners.
Multigang Installations
When installing more than one control in the same wallbox, it may be necessary to
remove all inner side sections prior to wiring (see diagram). Using pliers, bend side
section up and down until it breaks off. Repeat for each side section to be removed.
Removal of dimmer side sections reduces maximum load capacity. Refer to chart below
for maximum dimmer capacity.
Each Control Has Inside
Sections Removed
Dimmer Capacity Chart
Dimmer
No sides
1 side
Rating
removed
removed
600 W
600 W max.
500 W max.
NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts.
Installation
1
Turning OFF Power.
• Turn power OFF at circuit breaker (or remove fuse).
Shock Hazard. May result in serious injury or death.
WARNING
Turn off power at circuit breaker before installing the unit.
2
Removing Wallplate and Switch.
• Remove wallplate and switch mounting screws.
• Carefully remove switch from wall (do not remove wires).
Verify power
is OFF to
switch before
proceeding.
3
Identifying the Type of Circuit.
Different-colored screw (Common).
Actual location may vary.
OR
Ground (Bare
Copper or
Green Wire)
Ground (Bare Copper
or Green Wire)
SINGLE-POLE:
3-WAY:
Insulated wires connected
Insulated wires connected to three screws. One of
to two screws of the
these wires is connected to a screw of a different-
OR
same color. Replace with
color (not green) or labeled COMMON. MARK or
a SINGLE-POLE dimmer.
TAG this wire to identify it when wiring. Replace
See Step 5a.
with a 3-WAY dimmer. See Step 5b.
Wiring Device-Kellems
Hubbell Incorporated (Delaware)
Shelton, CT 06484
1-800-288-6000
www.hubbell-wiring.com
4
English
Disconnecting Switch Wires.
Important Note: Your wall switch may have two wires attached to the same screw (see
illustrations below for examples). Tape these two wires together before disconnecting.
Use the same procedure to wire your new dimmer as was used with the old switch.
One wire in the
backwired hole and
one to the screw.
2011, Article
®
Screw Terminals:
Turn screws to loosen.
Important Wiring Information
When making wire connections, follow the recommended strip lengths and combinations for the
supplied wire connectors. Note: Wire connectors provided are suitable for copper wire only. For
aluminum wire, consult an electrician.
Small:
Strip insulation 3/8" (10 mm) for 14 AWG wire
Strip insulation 1/2" (13 mm) for 16 or 18 AWG wire
Use to join one 14 AWG supply wire with one 16 or
18 AWG control wire.
Large:
Strip insulation 1/2" (13 mm) for 10, 12, or 14 AWG
wire
Strip insulation 5/8" (16 mm) for 16 or 18 AWG wire
Use to join one or two 12 or 14 AWG supply wires
with one 10, 12, 14, 16, or 18 AWG control wire.
5
Wiring the Dimmer.
• For installations involving more than one control in a wallbox, refer to the
section on Multigang Installations before beginning.
Do Not Remove
Outside Sections
5a - Single-Pole Wiring
Ground
(Green screw)
Middle Control Has Two
Side Sections Removed
2 sides
120 V~
removed
60 Hz
400 W max.
Dimmer
5b - 3-Way Wiring
Ground
(Green screw)
Copper screw
Tag
120 V~
Dimmer
60 Hz
6
Mounting Dimmer to Wallbox.
• Form wires carefully into the wallbox, mount and align dimmer.
• Install wallplate.
Start screws.
7
Turning ON Power.
• Turn power ON at circuit breaker (or replace fuse).
Tag
One continuous wire
to the screw.
Push-in Terminals:
Looped Wire:
Insert screwdriver. Pull
Turn screw to loosen.
wire out.
Twist wire connector
Be sure no bare wire
Large
Small
• Connect the bare copper or green
ground wire in the wallbox to the
green ground screw on the dimmer.
(See Important Note 3.)
• Connect one of the wires removed
from the switch to either of the
screws (or push-in terminal) on the
dimmer.
• Connect the other wire removed from
the switch to the other screw (or
push-in terminal) on the dimmer.
Note: To use a 3-Way dimmer (one
Ground
copper and two brass screws) in a
single-pole application, tighten the
Light
brass screw which is on the same
side as the copper screw and follow
instructions for single-pole wiring.
• NOTE: Only one dimmer can be used
in a 3-WAY circuit.
• Connect the bare copper or green
ground wire in the wallbox to the
green ground screw on the dimmer.
(See Important Note 3.)
• Connect the wire removed from the
different-colored screw on the switch
(marked or tagged wire) to the copper
screw on the dimmer. Remove tag
Tag
from wire.
Ground
• Connect one of the remaining wires
removed from the switch to either
brass screw on the dimmer.
• Connect the remaining wire removed
3-Way
from the switch to the remaining
Switch
Light
brass screw on the dimmer.
Align dimmer and
tighten screws.
Made and printed in the U.S.A.
1/11 P/N 037-210 Rev. A
PDS 2295 1/11
Gradateur à incandescence /
halogène 120 V
RAY600 Série
Puissance nominale de 120 V~ 60 Hz 600 W
Remarques importantes
Veuillez lire avant de procéder à l'installation.
1. AVIS : N'utiliser qu'avec des appareils d'éclairage incandescents ou halogènes
de 120 V installés en permanence. Pour éviter la surchauffe et d'éventuels
dommages à d'autres équipements, ne pas utiliser ce dispositif pour commander
l'intensité des prises de courant, des luminaires à tube fluorescent, des appareils à
moteur électrique ou des appareils alimentés par transformateur.
2. L'installer en respectant tous les codes d'électricité nationaux et locaux.
3. Lorsqu'il n'y a pas de « dispositif de mise à la terre » dans la boîte murale, le NEC
2011, Article 404-9(B) autorise l'installation en remplacement d'un gradateur sans
liaison de terre à condition d'utiliser une plaque frontale en plastique non
combustible. Pour ce type d'installation, encapuchonner ou retirer le fil de terre vert
du gradateur et utiliser une plaque frontale correspondante.
4. Pour les nouvelles installations, installer un interrupteur d'essai avant de faire la pose
du gradateur.
5. Protégez le gradateur de la poussière et de la saleté lorsque vous peignez ou rebouchez.
6. Un seul gradateur peut être utilisé dans un circuit à 3 voies.
tight.
7. La charge minimale recommandée est de 40 W.
is exposed.
8. Il est normal de sentir une chaleur au toucher du gradateur intelligent lorsqu'il fonctionne.
9. Nettoyer le gradateur avec un chiffon doux et humide seulement. Ne pas utiliser
de nettoyants chimiques.
Installation des gradateurs multiples
Lors de l'installation de plus d'un gradateur dans la même boîte murale, il peut être
nécessaire d'enlever toutes les sections latérales intérieures avant de faire le câblage
(voir ci-dessous). Avec des pinces, replier la section latérale de haut en bas jusqu'à ce
qu'elle se sépare. Répéter pour chacune des sections latérales à enlever. La dépose des
sections latérales du gradateur a pour effet de réduire la capacité de charge maximale.
Consulter le tableau ci-dessous pour connaître la capacité maximale du gradateur.
Tableau des capacités du gradateur
Puissance nominale
Aucun côté
du gradateur
enlevé
600 W
600 W max.
NEC est une marque de commerce de National Fire Protection Association, Quincy, Massachusetts.
Installation
1
Coupure de l'alimentation électrique.
• Couper l'alimentation au disjoncteur (ou retirer le fusible).
AVERTISSEMENT
2
Dépose de la plaque murale et de l'interrupteur.
• Enlever la plaque murale et les vis de montage de l'interrupteur.
• Retirer délicatement l'interrupteur du mur (ne pas enlever les fils).
3
Identification du type de circuit.
Mise à la terre (fil de
cuivre dénudé ou fil vert)
UNIPOLAIRE :
Les fils recouverts sont
raccordés à deux vis de la
même couleur. Remplacer par
un gradateur UNIPOLAIRE.
Voir l'étape 5a.
Français
®
Ne pas retirer
les sections
extérieures
Les sections intérieures de
Les deux sections latérales
chaque gradateur sont
du gradateur mitoyen sont
enlevées
enlevées
1 côté
2 côtés
enlevé
enlevés
500 W max.
400 W max.
Risque de choc. Peut entraîner de graves blessures
ou la mort. Couper l'alimentation au niveau
du disjoncteur avant d'installer l'appareil.
S'assurer que
l'alimentation
électrique est
coupée avant de
commencer.
Vis de couleur différente (neutre).
Son emplacement peut différer
de l'illustration.
OU
Mise à la terre (fil
de cuivre dénudé
ou fil vert)
Étiquette
3 VOIES :
Les fils recouverts sont raccordés à trois vis.
L'un de ces fils est connecté à une vis de
OU
couleur différente (pas verte) ou étiquetée
NEUTRE. MARQUER ou ÉTIQUETER ce fil pour
l'identifier lors du câblage. Remplacer par un
gradateur 3 VOIES. Voir l'étape 5b.
Continué au verso...
Fabriqué et imprimé aux É.-U.
1/11 N/P 037-210 Rev. A
PDS 2295 1/11