FIRE-RATED OMNIPANEL
DUAL-VALVE ACCESS PANEL
DESIGN SPECIFICATION
1. WALL CONSTRUCTION
a. Wood or metal stud construction
b. 16" or 24" on-center stud construction.
c. Double-layer ⅝" gypsum construction with 2-hour fire rating.
d. Panels cannot be installed back to back.
Fire-Rated finish kit includes:
Frame, hole-insert strips (2), and frame extension. Available separately.
2. PIPE/PANEL SUPPORT
a. Each panel shall be installed in a separate stud bay and attached to the
stud via brackets (fig 2). Fire rating does not apply to installations of two or
more panels in the same stud bay.
b. Supplied brackets.
c. Supply lines to be installed using ordinary methods.
d. Drain line to be supported using ordinary methods.
3. PIPE MATERIAL
a. 2" or larger metallic, PVC, or ABS DWV pipe.
b. Metallic or plastic water supply pipe.
4. FIRE-RATED RESINS
Sioux Chief fire-rated OmniPanel uses fire-rated resin.
NOTE: Gaps up to ½" around panel can be sealed with drywall plaster.
Larger gaps require firestop sealant applied to opening spanning entire drywall depth
THE FIRE-RATED OMNIPANEL IS CERTIFIED BY INTERTEK
TO THE FOLLOWING FIRE RATING STANDARDS:
ASTM E-814
2hrs (F), 1hr 55mins (T) for 2-hour design
CAN/ULC S115
2hrs (FH), 1hr 55mins (FTH) for 2-hour design
Sioux Chief Manufacturing Company
FIGURE 1
Finish
Kit
FINISH INSTALLATION
|
P: 1.800.821.3944
|
F: 1.800.758.5950
3a
2b
1c
3b
|
www.siouxchief.com
1a/b
10-19