AERMEC VMF-E18X Manual De Instrucciones E Instalación página 20

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

BOARD INSTALLATION AND CONNECTIONS
• The VMF-E18X Kit includes the
system with connection cables
to the Inverter Control Module.
The cables are wired with connectors
for quick connection.
The installation of the VMF-E18X kit
requires that standard control board
and connection cables to the Inverter
Control Module (Signal and Supply) are
removed from the fan coil.
• Mount the thermostat housing to the
side of the fan coil units, on the con-
nections that were of the control board.
• Remove the cover of the thermostat
housing.
• Connect the inverter control module
VMF-E18X to the thermostat using
the system with connection cables
supplied with the VMF-E18X kit.
Check the connection with the wiring
diagram.
• WARNING: make an earth connection
for the thermostat board.
DANGER: it is compulsory to tighten
the screw on the side of the fan coil, as
this is what allows the earth connection
of the entire system.
• Connect the power supply cables. Warn-
ing: respect the L and N polarities.
• Connect the electric cables of the air
temperature sensor (SA).
• Connect the electric cables of the water
temperature sensor (SW).
• Connect the electric cables of the sec-
ondary water temperature sensor (SW1),
in 4-pipe hydronic systems.
• Connect the cables for the external
contact (if envisaged).
• Connect the cables for the presence
sensor (if envisaged).
• Connect the cables for the microswitch
(if envisaged).
• Connect the mains and RS485 power
supply cables (if connected to the
mains). DANGER: connect the cable
shield to the ground.
• Connect the TTL mains cables (if con-
nected to the mains).
• Connect the cables of the control panel
(if envisaged).
• Check that all the connections and rela-
tive cables are well fixed.
• Arrange the cables so there is no risk
of them being cut, crushed, jerked,
scraped, or generally damaged.
• Check that the board fuse is undamaged
and possesses the necessary features.
• Close the housing with the cover.
• Fix the power supply cables and valve
cables using the cable clamp.
WARNING: Keep separate electri-
cal connections from water con-
nections. Water connections and
drain should be on the side oppo-
site of the electrical connections.
20
AVMFE18LJ1701 - 6795748_02
DANGER: it is compulsory to tighten the screw on the side of the fan coil, as this is
what allows the earth connection of the entire system.
FCXI 2_
FCXI 3_
FCXI 4_
FCXI 5_
FCZI 2__
FCZI 3__
FCZI 4__
FCZI 5__
W0F0201
W0F0301
FCXI 8_
FCZI 7__
FCZI 9__
W0F0102
R00202
R00301
R00401

Publicidad

Tabla de contenido
loading

Tabla de contenido