Trimpots Function - Weq EA08A Manual De Instalación Y Operación

Regulador automático de tensión
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3.
IDENTIFICATION OF CONNECTION TERMINALS
E1- 110, 220, 380/440 : Sensing voltage (110/220/380 Vac).
F+, F- : Connection for alternator field.
X1, X2, Z1, Z2 : The power input can be Self-Excited Shunt, PMG, Harmonic, Full Harmonic and Auxiliary Winding.
S1-S2 : Connection for CT 5A of parallel operation.
S2-S3 : Connection for CT 1A of parallel operation.
VR-VR : Connection for potentiometer 1kΩ/1W (It should be isolated using twisted cable for connection).
A1-A2 : Analog input voltage. A remote DC voltage to adjust the output voltage of the alternator.
ATTENTION
1. Before connecting the regulator to the alternator, verify in the installation manual, the rated sensing
voltage.
2. Incorrect voltage and frequency adjustment can damage AVR.
3. If no potentiometer is used, keep EXT.VR terminal connected. (shorted).
4.

TRIMPOTS FUNCTION

Trimpot
Function
VOLT
Voltage adjustment
STAB
Stability adjustment
UFRO
Under frequency adjustment
TRIM
Fine adjustment
Adjust Reactive
DROOP
compensation
DIP
voltage drop adjustment
5.
DIP SWITCH FUNCTION
KW
< 90 KW
SW
1
OFF
2
OFF
Freq
.
50 Hz
SW
3
OFF
Turning it clockwise to increase voltage and counterclockwise decreases.
Turning it clockwise, dynamic response will be slower.
Turning it clockwise to increase U/F and counterclockwise decreases.
Adjust analog input voltage.
Turning it clockwise, increases the reactive compensation range.
Adjust the slope of the voltage / frequency characteristic (Hz).
90 − 500 KW
> 500 KW
OFF
ON
ON
ON
60 Hz
ON
www.weg.net
Adjustment
Automatic Voltage Regulator | 4