Dual-Feed Wiring for Two (2) PB/ELVI Interfaces on One
Zone - 120V and 220-240V
The load breaker/MCB can be on a different phase than the control
breaker/MCB.
LOAD NEUTRAL
LOAD
Single-Feed Wiring for PB/ELVI
230V
The PB/ELVI may be on the same circuit as the Control
Unit only if the total load does not exceed the rating of
the breaker.
LOAD
2:22 PM
Page 4
NEUTRAL
4
3
2
HOT/LIVE
1
ZONE
LOAD NEUTRAL
LOAD
N
H/L
H/L
N
NEUTRAL
4
3
2
HOT/LIVE
1
ZONE
LOAD NEUTRAL
Tu-Wire Dimming Ballast
When using a PB to control a Lutron Tu-Wire dimming bal-
I
last, the associated zone on the GRAFIK Eye
Control Unit must be set to the Tu-Wire load type. Please
see the GRAFIK Eye 3000 Series Installer's Guide for more
details.
H/L
The PB 230V must not be used with Tu-Wire ballasts
I
N
because the Tu-Wire load type is not available on 230V CE
models of the GRAFIK Eye Control Unit.
N
H/L
Dual-Feed Wiring for PB/ELVI
230V
The load breaker/MCB can be on a different phase than the control
breaker/MCB
.
LOAD
4
®
3000 Series
H/L
N
NEUTRAL
4
3
2
HOT/LIVE
1
ZONE
LOAD NEUTRAL
N
H/L