Function
BUTTONS SCREEN
- Programming iNELS system functions on each button on the screen units EST3 is the same as
programming other digital inputs or events for input or button units.
- Buttons can be confi gured as well as other inputs in the system, both for short and also long
press (> 1.5 s).
- Buttons (icons) on the screen can be used instead of control outputs for visualization of one of
the digital outputs of the system iNELS. This is made possible by assigning button to the desired
output.
- In doing so, the button (icons) on the screen EST3 will become signal lamps (illuminated button),
showing the state of the associated output.
HEATING CONTROL SCREEN
- On the temperature control screen, the temperature of the selected heating circuit can be
corrected in the range of ±3, ±4 or ±5 °C.
- The virtual wheel can be used for temperature correction, where you can drag your fi nger across
the screen to control the temperature by half a degree Celsius.
- The temperature correction can also be used instead of the virtual wheel symbols "+ " and "- " .
RGB LAMP AND LIGHT SOURCE CONTROL SCREEN
- The RGB light sources control screen contains controls for managing the desired color and
brightness of the RGB light sources.
- RGB control screen function is set up so that the colors R, G, B are bound together and simulate
the signal level on analog inputs R, G, B and the resulting brightness of the lamp is linked to a
simulated analog input 0 to 100%.
- The RGB control display is comprised of several elements and buttons.
- A long press (touch) on the ON/OFF controls the central setting of RGB components and lamp
brightness - on/off .
- Buttons
in the upper half of the screen are for setting the lamp brightness from 0-100%
in 5% increments (see adjustable brightness indicator in %).
- Buttons
in the lower half of the screen are for setting the color comfort and accelerated
lamp RGB control. The buttons have a lock function. When pressing
button, the analog inputs are automatically set to the maximum value of individual color
components, which appears as a resulting white light at the RGB light source output when
these components are mixed. Then simply adjust the brightness intensity at the output. When
pressing (touching) the button
button
automatically unlocks, and the "RGB-based color illumination" settings button
locks..Now the values of analog inputs of individual RGB color components are preset
according to the set cursor in the color wheel of the RGB scale on the EST3.
ADDITIONAL INFORMATION
- Info
gives information on the device and fi rmware version.
- Clicking the icon
brings you to the settings menu, used to edit the EST3 (password to enter
Settings is 1111 by default).
- The icon
returns to the buttons panel.
- The system time is displayed in the upper right corner of the screen.
- All inputs and outputs on the EST3 unit can be freely programmed and parameterized using the
iDM3 program.
Technical parameters
Display
Type:
Aspect ratio:
Visible area:
Backlight:
Touchpad:
Display:
Number of points:
Color Depth:
Power supply
Supply voltage / tolerance:
Dissipated power:
Rated current:
Connection
Connection:
Connecting conductors
profi le:
Operating conditions
Operating temperature:
Storing temperature:
Protection degree:
Overvoltage category:
Pollution degree:
Operating position:
Installation:
Dimensions and weight
Dimensions:
Weight:*
* Weight is listed with plastic frame.
TECHNICAL SUPPORT | E-mail: support@inels.com | Mobil: +420 778 427 366 | Tel.: +420 573 514 276, +420 573 514 211 | Fax: +420 573 514 227 | www.inels.com
Made in Czech Republic
"white illumination"
"RGB-based color illumination", the "white illumination",
EST3
colored TFT LCD
3:4
52.5 x 70 mm
active
4-wire resistive
3.5"
240 x 320
16.7M (24 bit color)
27 V DC, -20 / +10 %
max. 2 W
150 mA (at 27V DC)
terminals
max. 2.5 mm
2
/
2
1.5 mm
with sleeve
0 .. +55°C
- 20 .. +70°C
IP20
II.
2
any
installation box
94 x 94 x 36 mm
120 g
ELKO EP, s.r.o. | Palackého 493 | 769 01 Holešov, Všetuly | Czech republic | e-mail: elko@elkoep.com
General instrucions
CONNECTION TO THE SYSTEM, INSTALLATION BUS
iNELS3 peripheral units are connected to the system through the BUS installation. Installation
BUS conductors are connected to the terminal units to BUS+ and BUS- terminals, wires cannot be
interchanged. For installation of BUS it is necessary to use a cable with a twisted pair of wires with
a diameter of at least 0.8 mm, the recommended cable is iNELS BUS Cable, whose features best
meet the requirements of the BUS installation. Bearing in mind that in terms of all the properties
is it is possible in most cases also use the cable JYSTY 1x2x0.8 or JYSTY 2x2x0.8, however it
is not recommended as the best option. In the case of a cable with two pairs of twisted wires
it is not possible to use the second pair of the other for modulated signal due to the speed of
communications; it is not possible within one cable to use one pair for one segment BUS and the
second pair for the second segment BUS. For installation of BUS it is vital to ensure that it is kept
at a distance from the power lines of at least 30 cm and must be installed in accordance with its
mechanical properties. To increase mechanical resistance of cables we recommend installation
into a conduit of suitable diameter. BUS topology installation is free except for the ring, wherein
each end of the bus must terminate at the terminals BUS + and BUS- peripheral unit. While
maintaining all the above requirements, the maximum length of one segment of the installation
BUS can reach up to 500 m. Due to the data communication and supply of units in one pair of wires,
it is necessary to keep in mind the diameter of wires with regards to voltage loss on the lead and
the maximum current drawn. The maximum length of the BUS applies provided that they comply
with the tolerance of the supply voltage.
CAPACITY AND CENTRAL UNIT
It is possible to connect to the central unit CU3-01M or CU3-02M two independent BUSes by means
of terminals BUS1+, BUS1- and BUS2+, BUS2-. It is possible to connect to each BUS up to 32 units,
so it is possible to connect directly to the central unit a total of 64 units. It is necessary to comply
with the requirement of a maximum load of one BUS line - maximum up to 1000 mA current. When
connecting units which draw greater than 1A, BPS3-01M with 3A sampling can be used. It is the
sum of the rated currents of the units connected to the BUS line, other units can be connected
using the units MI3-02M, which generate further BUSes. These are connected to the CU3 unit via
the system BUS EBM and you can connect a total of 8 units via EBM BUS to the central unit MI3-02M.
SUPPLYING THE SYSTEM
For supplying power to system units, it is recommended to use the power source of ELKO EP titled
PS3-100/iNELS. We recommend backing up the system with backup batteries connected to the
source of PS3-100/iNELS (see sample diagram of connecting the control system).
GENERAL INFORMATION
To operate the unit, it is necessary that the unit is connected to a central unit CU3 series, connected
to the central unit of the system CU3, or to a system that already contains this unit as its expansion
to include further system.
All unit parameters are set through the central unit CU3-01M in the software iDM3.
There is LED diode on the PCB for indication of supply voltage and communication with the
central unit series CU3. In case that the RUN diode fl ashes at regular intervals, so there is standard
communication between the unit and BUS. If the RUN diode lights permanently, so the unit is
supplied from BUS, but there is no communication between BUS and unit. In case that RUN diode
is OFF, so there is no supply voltage on the terminals BUS+ and BUS-.
Warning
Before the device is installed and operated, read this instruction manual carefully and with full
understanding and Installation Guide System iNELS3. The instruction manual is designated for
mounting the device and for the user of such device. It has to be attached to electro-installation
documentation. The instruction manual can be also found on a web site www.inels.com. Attention,
danger of injury by electrical current! Mounting and connection can be done only by a professional
with an adequate electrical qualifi cation, and all has to be done while observing valid regulations.
Do not touch parts of the device that are energized. Danger of life-threat! While mounting,
servicing, executing any changes, and repairing it is essential to observe safety regulations, norms,
directives and special regulations for working with electrical equipment. Before you start working
with the device, it is essential to have all wires, connected parts, and terminals de-energized. This
instruction manual contains only general directions which need to be applied in a particular
installation. In the course of inspections and maintenance, always check (while de-energized) if
terminals are tightened.
2/2