Descargar Imprimir esta página

Wiring Information - Eaton Greengate RIM 347 Guia De Inicio Rapido

Módulo del relé de interfaz

Publicidad

Idiomas disponibles

Idiomas disponibles

Wiring Information

Wiring Information
1.
Ensure that the lighting panel's transformer is wired to
an emergency circuit.
2.
Connect the Relay Interface Module's yellow and purple
low voltage wires into the provided terminal block.
To force all relays ON, connect to the ON and +24V
position. To force all relays OFF , connect to the OFF and
+24V position. Yellow and purple wires are not polarity
sensitive.
3.
Connect the relay interface module to the normal
power monitoring circuit. Wire the neutral wire to the
white wire. Wire the hot to the colored wire:
Brown = 347 VAC.
Please see diagrams below for further details.
Relay Interface Wiring Diagram:
Connector on Override Card
Yellow (18 AWG)
NC
Violet
(18 AWG)
C
SPDT
Relay
NO
2
www.eaton.com/lighting systems
ON + OFF
To Override ON:
Connect dry contact
between on override and
+24 VDC. When contact
closes, all relays are
forced ON. Card Contacts
will close when normal
power is lost.
To Normal Power
347VAC = Brown
Neutral = White
Override Card Low Voltage Connection Point:
External Override is Located Behind the
Override Switch on the Override Card.
External Override
ON Override
ON + OFF
+24VDC
OFF Override
ON Override
+24VDC
To Override ON:
OFF Override
Connect dry contact between ON
override and +24 VDC. When contact
closes, all relays are forced ON.
To Override OFF:
Connect dry contact between OFF
override and +24 VDC. When contact
closes, all relays are forced OFF.
CC15
CC16
CC13
CC14
CC11
CC12
CC9
CC10
CC7
R7
R8
CC8
R5
R6
CC5
CC6
R3
R4
CC3
CC4
CC1
R1
R2
CC2

Publicidad

loading