MODULAR PHOTOCELL LIGHTING CONTROL with separate probe
1 DIN
PE - DEICNN009
03/19
1 - Technical data
1
2
Supply voltage:
Type of output:
Operating status signal LED
Relay command:
Threshold intervention (lux) adjustment trimmer:
Lux threshold adjustment
Selector for operating mode selection:
trimmer
Delay time at switching ON and switching OFF:
10
0
100
Hysteresis:
LUX
OFF
Operating mode
x10
Section of the cables to the module terminals:
x1
setting rotary selector
Protection level:
Probe with precision photodiode sensor:
0....100/1000 Lux
Operating temperature limits of module:
Operating temperature limits of probe:
3
4
Storage temperature limits:
probe
Installation:
L
N
CE reference standards:
Ability to control low safety voltage SELV circuits
WARNINGS!
Example of maximum operating power:
Read this manual carefully before using the
&
product as it provides important guidelines
regarding safety, installation and use. The manual
must be preserved with care for future reference.
resistive
Caution! Installation by person
DEVICE DESCRIPTION
with electrotechnical expertise only.
The electronic twilight switch controls the switching ON and OFF of outdoor lighting systems.
Before starting any operations on the device,
Among the various uses, the most common is the automatic illumination of streets, shop signs, stairs or
disconnect the 230V~ mains power supply
gardens as the sunlight wanes (twilight).
The switch closes the contact when the light level falls below the set threshold and it remains closed
This equipment will be intended only for use for which it
until the threshold is next exceeded. The contact is opened and closed with a delay (fixed setting) T on
was specifically built.
approx. 15 seconds and T off approx. 30 seconds, in order to prevent false switch on caused by brief
changes in brightness such as lightening, car headlights, etc.
DISPOSAL OF OLD ELECTRICAL & ELECTRONIC EQUIPMENT
The device is equipped with a rotary selector for selecting the operating mode, a trimmer for adjusting
This symbol on the product or its packaging to indicates that this
the LUX threshold and a Led light for signalling the operating status.
product shall not be treated as household waste. Instead, it shall
One important feature of the device is the intelligent relay command of the "zero crossing" relay which
be handed over to the applicable collection point for the recycling
optimises the enabling and disabling of the load, increasing the lifetime relay.
of electrical and electronic equipment .
ROTARY SELECTOR WITH 4 OPERATING POSITIONS and LUX THRESHOLD ADJUSTMENT TRIMMER:
Lux threshold adjustment trimmer
from 0 to100 Lux
10
0
100
LUX
x10
OFF
position: x1
(Lux scale)
x1
twilight operation
10
0
100
LUX
x10
OFF
position: OFF
x1
Relay always disabled
LED SIGNALS (LED on front
)
Selector position
T on
(Delay time at switching ON)
x1
(twilight)
fast blinking
x10
(twilight)
fast blinking
OFF
(relay always disabled)
(relay always enabled)
Important: the switched off LED means the device is not powered.
230V~ +/- 10%, 50 Hz
relay with NO free contacts (without Cadmium)
with potential of 16A / 250V~
type «zero-crossing»
0...100 Lux / 0...1000 Lux
4 positions
T on = 15 sec / T off = 30 sec
dynamic type
1 mm² ÷ 6 mm²
IP 20 (module)
IP 65 (probe with cable diam. 4 ÷ 8 mm)
Cd - Free
- 10 °C ÷ +55 °C
- 30 °C ÷ +65 °C
- 20 °C ÷ +65 °C
DIN rail (module) - outdoor (probe)
LVD/EMC
EN60669-2-1
16A
3600W
1000W
1000W
(28x36W)
(28x36W tot. 140 µF)
Lux threshold adjustment trimmer
10
from 0 to1000 Lux
(example in figure: trimmer set to 100 Lux)
0
100
LUX
x10
OFF
position: x10
x1
twilight operation
10
0
100
LUX
x10
OFF
position:
x1
Relay always enabled
T off
Relay ON
Relay OFF
(Delay time at switching OFF)
blinking
slow blinking
blinking
slow blinking
slow blinking
fixed
2 - ELECTRICAL CONNECTION
Important: the installation and electrical connections of
devices and equipment must be performed by qualified
personnel in conformity with current standards and
regulations.
WARNING: in case of particularly reactive loads (e.g.
fluorescent or HID or electronic lamps, etc.) or with a cosj
value lower than in-dicated in the technical data, the relay
could suffer damage. It is advisable in such instances to use a
suitably rated external or solenoid switch.
.
The manufacturer does not assume any responsibility
concerning the use of the products, which must conform to
particular environmental and/or installation standards.
CAUTION: the electrical connection to the separate
probe must be made by a twin cable that has a minimum
external diameter of 4 mm, a maximum of 8 mm
and with the section of each conductor 0.75 ÷ 1.5 mm .
2.2 - Installation of the probe
Installation on wall or pole using the fixing bracket provided.
• Fix the bracket to the wall
• Make the electrical connections to the probe
• Insert the body of the probe onto the bracket until it locks (the tooth snaps on the bracket)
35 x 7W
25 x 23W
Probe
Fixing bracket
CAUTION: once the connection has been completed, the electrical parts will be live: do not open
the protective cover without first disconnecting the 230 V~ supply.
3 - DESCRIPTION OF THE OPERATING MODES (4 position rotary selector)
(Lux scale)
position x1
position x10
in twilight mode
When the light intensity detected by the probe is lower than the value set
on the "lux adjustment" knob, the relay will close the contact after a brief
delay (about 15 sec) called T on.
On the contrary, when the light intensity detected by the probe exceeds
the value set on the "lux adjustment" knob, the relay will open the contact
after a brief delay (about 30 sec) called T off.
LED
Relay
T on
fast blinking
fast blinking

2.1 - Electrical connections (

Turn off the mains supply)
Connect the 230 V~ supply to the L (line) and N (neutral) terminals.
Connect the load as indicated in figure:
- neutral (N) directly to the lamp
- terminal 1 to the line (L)
- terminal 2 to the lamp.
Connect the wires coming from the probe to terminals 3 and 4 of the twilight switch.
2
230 V~
To ensure correct operation, the
probe must be installed so as not
to be influenced by the switching
on of the lamps
Gaskets
Fixing
bracket
YES
(note: the probe is also available as a spare part)
position OFF:
Relay always disabled
This feature is useful for prolonged switch OFF (e.g. holidays), without
the need to modify the Lux threshold setting.
LED
Relay
position
:
Relay always enabled
T off
This function is useful for carrying out tests to verify correct installation.
LED
Relay
The manufacturer reserves the right to introduce any modification without prior notice.
EN
Probe
cable
max 50 m
Cover
Terminals
Base
Fixing
cable
screw
passage guide
Connector
gasket rubber
Cable-locking
nut