Wiring the EtherNet/IP
Module to InView Display
Below is a picture and description of the InView EtherNet/IP and
DeviceNet Interface module and its connectors with relation to an
InView Display.
Customer-supplied
Ethernet/DeviceNet cable
through NEMA-rated
supplied connector
PENI Power Cable
The PENI module requires a separate 24V dc power supply. The
power supply cable diameter must be between 0.069 in to 0.260 in
(1.75 mm to 6.60 mm). The PENI module Ethernet cable installed must
have a radius of at least 0.5 in (12.7 mm).
1. Disconnect power to InView display.
ATTENTION
!
2. Remove the power supply cover (on 2706-P4x) by unscrewing
its six screws. Set the screws and cover aside for later step.
Back of InView Display (P42, P43, P44)
2706-PENI/2706-PDNI
NEMA Type 4X Enclosure with Removable Cover
Torque Enclosure Cover screws to 1.1 Nm (10 in-lb).
Hazardous voltage. Contact with high voltage
may cause death or serious injury. Always
disconnect power to the InView display prior
to servicing.
2706-P42, 2706-P43, 2706-P44
InView EtherNet/DeviceNet Module
Serial cable to be
connected to terminal
block inside power supply
cover on back of InView
display
Publication 2706-IN010C-MU-P
5