• EEI:
The benchmark for most efficient circulators is EEI ≤ 0,20
* The pump is equipped with a power limiting function which provides protection
against overload. This can have an effect on the output depending on operation.
5.3 Suitable fluids
• Heating water according to VDI 2035.
• water/glycol mixture at a mixing ratio of max. 1:1. If glycol is added, the delivery
data of the pump must be corrected according to the higher viscosity, depending
on the percentage mixing ratio.
• SALMSON's approval must be obtained for use of other media.
5.4 Scope of supply
• Circulating pump + gaskets + connector.
• Installation and operating instructions.
6 Description and operation
6.1 Pump (Fig. 1)
• The pump consists of a hydraulic system, a glandless pump motor with permanent
magnet rotor and an electronic control module (ECM technology) with integrated
frequency converter.
• The control module includes a display for setting all parameters and for displaying
the current electricity consumption in W and the cumulative electricity
consumption in kWh since commissioning.
7 Installation and electrical connection
DANGER! Danger of death!
Incorrect installation and electrical connection can result in fatal injury.
• Installation and electrical connection may only be carried out by qualified
personnel and in accordance with the applicable regulations!
• Adhere to regulations for accident prevention.
7.1 Recept of the product
Unpack the pump and recycle packaging to take care of the environment.
7.2 Installation
• Only install the pump after all welding and soldering work has been completed
and, if necessary, the pipe system has been flushed through.
• Install the pump in a readily accessible place for easy inspection and dismantling.
• When installing in the feed of open systems, the safety supply must branch off
upstream of the pump (DIN EN 12828).
Salmson
refer to name plate data
English
21