Technical parameters
Inputs
Temperature measuring:
Scope and accuracy of
temp. measurement:
Humidity measurement:
Humidity measure. range:
Humidity measure. accurancy:
Inputs:
Resolution:
External temperature sensor:
Type external sensor:
Temp. measurement range:
Temp. measurement accuracy:
Buttons
Number of control buttons:
Type:
Indication:
Display
Display:
Resolution:
Outputs
Acustic output:
Tactile output:
Communication
Installation BUS:
Power supply
Supply voltage / tolerance:
Dissipated power:
Rated current:
Connection
Terminals:
Operating conditions
Relative humidity:
Operating temperature:
Storing temperature:
Protection degree:
Overvoltage category:
Pollution degree:
Operation position:
Installation:
Dimensions and weight
Dimensions:
Weight:
TECHNICAL SUPPORT | E-mail: support@inels.com | Mobil: +420 778 427 366 | Tel.: +420 573 514 276, +420 573 514 211 | Fax: +420 573 514 227 | www.inels.com
Made in Czech Republic
GRT3-50
YES, built-in temperature sensor
0.. +55 °C;
0.3 °C from the range
YES
0 .. 99 % RH
± 3 % Relative humidity
2x AIN/DIN
by setting 10-bit
YES, the connection between
AIN1/DIN1 and AIN2/DIN2
TC/TZ
-20 °C .. +120 °C
0.5 °C from the range
5
capacitive
coloured illuminated symbol
colored TFT, 20 x 25.5 mm
240 x 240 pixels
piezo-changer
vibration motor
BUS
27 V DC, -20 / +10 %
max. 0.5 W
85 mA (at 27V DC), from BUS
2
0.5 - 1 mm
max. 80 %
-20 .. +55 °C
-30 .. +70 °C
IP20
II.
2
any
on the wall, observing the conditions for correct
installation of the thermostat
94 x 94 x 36 mm
156 g
ELKO EP, s.r.o. | Palackého 493 | 769 01 Holešov, Všetuly | Czech republic | e-mail: elko@elkoep.com
Warning
Before the device is installed and operated, read this instruction manual carefully and with full
understanding and Installation Guide System iNELS3. The instruction manual is designated for
mounting the device and for the user of such device. It has to be attached to electro-installation
documentation. The instruction manual can be also found on a web site www.inels.com. Attention,
danger of injury by electrical current! Mounting and connection can be done only by a professional
with an adequate electrical qualifi cation, and all has to be done while observing valid regulations.
Do not touch parts of the device that are energized. Danger of life-threat! While mounting, servicing,
executing any changes, and repairing it is essential to observe safety regulations, norms, directives
and special regulations for working with electrical equipment. Before you start working with the
device, it is essential to have all wires, connected parts, and terminals de-energized. This instruction
manual contains only general directions which need to be applied in a particular installation. In the
course of inspections and maintenance, always check (while de-energized) if terminals are tightened.
2/2