FACTORY SETTINGS

Regulating mode:
= Minimum proportional differential pressure regulation
14.

TYPES OF ALARM

No. of curve height blinks
2 Blinks
3 Blinks
4 Blinks
5 Blinks
Alarm Code
E1
E2
E3
E4
E5
15.
INSTALLATION – EVOSTA2 SOL
Always switch off the mains power supply before working on the electrical or
mechanical part of the system. Wait for the warning lights on the control panel to go
out before opening the appliance. The capacitor of the direct current intermediate
circuit remains charged with dangerously high voltage even after the mains power has
been turned off.
Only firmly cabled mains connections are admissible. The appliance must be earthed
(IEC 536 class 1, NEC and other applicable standards).
Ensure that the voltage and frequency on the data plate of the EVOSTA2 SOL circulator
are the same as those of the power mains.

15.1 Mechanical installation

A
ENGLISH
TRIP: loss of motor control, may be caused by incorrect parameters,
blocked rotor, disconnected phase, disconnected motor
SHORT CIRCUIT: short circuit on phases or between phase and earth
OVERRUN: software fault
SAFETY: safety module error, may be caused by a sudden overcurrent or
other hardware faults of the board
DRY RUN
TRIP: loss of motor control, may be caused by incorrect parameters,
blocked rotor, disconnected phase, disconnected motor
SHORT CIRCUIT: short circuit on phases or between phase and earth
OVERRUN: software fault
SAFETY: safety module error, may be caused by a sudden overcurrent or
other hardware faults of the board

Table 7: Types of Alarm

Figure 12: Mounting EVOSTA2 SOL

49
Alarm Description
EVOSTA2
EVOSTA3
C
B