Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

3. Apply power to the terminal.
Power Terminal Block (fixed)
120/240V ac, 3 Wire,
U.S. Color Code
L1
Black (Line)
White
(Neutral)

Connecting DC Power

The L1 and L3 versions (e.g., Catalog No. 2711-K5A1L1 or 2711-K5A1L3) of the
PV550 terminals connect to a 24V dc power source.
The table below shows the electrical ratings for the DC versions of the terminals.
Electronic circuitry and an internal fuse protect the terminals from reverse polarity
and over-voltage conditions
Terminal Type
PV550
• Do not connect the PanelView terminal to an AC power
ATTENTION
• The PanelView 550 terminal is designed for safe use when
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
120/240V ac,
3 Wire, European
Harmonized Color Code
L2
GND
L1
L2
GND
Green
Brown (Line)
(Earth Ground)
(Protective Earth)
Blue
(Neutral)
To Power Source
Supply Voltage
Power Consumption
18 to 30V dc,
12 Watts maximum
(24V dc nominal)
(0.5 Amps @ 24V dc)
source. Connecting to an AC power source may damage
the terminal.
installed in a suitably rated NEMA Type 12, 13, 4X (indoor
use only), IP54 or IP65 enclosure.
PanelView 550 Terminals
11
Green/Yellow