Descargar Imprimir esta página

Eaton Vaporgard Pro P2LM2 Serie Información De Instalación Y Mantenimiento página 2

Publicidad

Idiomas disponibles

Idiomas disponibles

DIMENSIONS CONTINUED
PENDANT
8 3/4
[221.7]
4 1/2
[114.7]
VLA1 1/2" NPT HUB
VLA2 3/4" NPT HUB
VLA3 1" NPT HUB
4 11/16
[119.8]
3 7/8
[99.2]
2 1/8
[53.9]
WIRING DIAGRAMS
NOTE: Use wire connectors/level nuts L, N and GND/PE for field wiring only. Purple and gray leads/connectors shall not be used.
2-COND LEVER NUT
3-COND LEVER NUT
DRIVER
RED
L
BLK
PURPLE
WHT
GREY
N
BLK
2-COND LEVER NUT
GND/P.E.
DRIVER WAGO (ONLY
INTERNAL GROUND SCREW
POPULATED WHEN MOUNTING
(ONLY POPULATED WHEN
MODULE INCLUDED)
MOUNTING MODULE
INCLUDED)
IF 1884 • 06/19
Copyright © 2019, Eaton's Crouse-Hinds Division
8 3/4
CEILING
[221.7]
JUNCTION
BOX
4 9/16
[ 116.0]
5
2 1/8
[53.4]
3 7/8
[98.5]
5-CONDUCTOR LEVER NUT
RED
LED
LED
LED
LED
BLK
5-CONDUCTOR LEVER NUT
MOUNTING MODULE (MAY
NOT BE INCLUDED WITH HEAT
AC
SINK ASSEMBLY)
FIELD ASSEMBLED LUMINAIRES
Complete lighting fixture consists of cover, optional wall or junction box and LED housing
VXW2
1/4
[ 7.1]
VLA1
VLA2
VLA3
3/4" NPT HUB
1/2" REDUCER SUPPLIED
MAINTENANCE
5 3/4
[146.2]
1.
Perform visual, electrical and mechanical inspections on a regular
basis. The environment and frequency of use should determine this.
However, it is recommended that checks be made at least once a
year. We recommend an Electrical Preventive Maintenance Program
as described in the National Fire Protection Association Bulletin NFPA
No. 70B: Recommended Practice For Electrical Equipment Maintenance
(www.nfpa.org).
2.
The lens should be cleaned periodically to ensure continued lighting
performance. To clean, wipe the lens with a clean, damp cloth. If this
is not sufficient, use a mild soap or a liquid cleaner such as Collinite
NCF or Duco #7. Do not use an abrasive, strong alkaline or acid
cleaner. Damage may result.
3.
Visually check for undue heating evidenced by discoloration of wires
or other components, damaged parts or leakage evidenced by water or
corrosion in the interior. Replace all worn, damaged or malfunctioning
components, and clean gasket seals before putting the luminaire back
into service.
4.
Electrically check to make sure that all connections are clean and tight.
5.
Mechanically check that all parts are properly assembled.
6.
To prevent heat build-up, remove dust from the fins on the LED housing,
using a soft brush or air pressure.
7.
LED arrays are not user serviceable. If service is required, replace
entire LED housing assembly, including driver.
REPLACEMENT PARTS
Vaporgard luminaires are designed to provide years of reliable lighting
performance. However, should the need for replacement parts arise,
they are available through your authorized Eaton's Crouse-Hinds Division
distributor. Assistance may also be obtained through your local Crouse-Hinds
representative.
Crouse-Hinds Sales Service Department, 1201 Wolf Street, Syracuse, New York
13208, Phone (866) 764-5454.
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof
are not guaranteed. In accordance with Eaton's Crouse-Hinds Division's "Terms and Conditions of Sale," and since conditions of use are outside our control, the purchaser should
determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.
Page 3
VXF 10 VXFT 10
VXF 20 VXFT20
VXJ4
VXT20
VLHR
VAPORGARD P2LM2/P3LM2 SERIES
Complete luminaire consists of LED housing and
cover: a VLA pendant, or a VLHR adapter and VX
P2LM2/P3LM2
mounting module shown
LED housing
FIGURE 6
Eaton's Crouse-Hinds Division
1201 Wolf Street, Syracuse, New York 13208 • USA
Copyright © 2019
VXF 10 VXFT 10
VXF 20 VXFT20
IF 1884
Revision 1
New 06/19

Publicidad

loading

Este manual también es adecuado para:

Vaporgard pro p3lm2 serie