Descargar Imprimir esta página

System Sensor L Serie Manual De Instrucciones página 2

Publicidad

Idiomas disponibles

Idiomas disponibles

3. INSTALL MOUNTING PLATE.
When securing the mounting plate to the electrical box or back
box, do not over-tighten mounting plate screws.
FIGURE 5. MOUNTING SCREW LOCATIONS
Mounting
Locations
Note: Mounting plate offers four locations for flexibility in choice of
back box. If possible, use all mounting screw-holes on the selected
electrical box or back box. Use only the screws provided with the
product.
Note: Check that the mounting plate is flush with the wall (as
described in Step 1) so that the final installation will also be flush
with the wall.
4. SECURE THE DEVICE TO THE MOUNTING PLATE.
To provide proper electrical connections, the appliance must be
properly seated on the mounting plate and the product-mounting
screw on the front of the device must be securely fastened.
– Optional: If the captive screw is to be replaced with a tamper-
resistant screw (provided), do that now.
– Use the "Keying Feature": There are two tabs at the top of the
device's back side. These match up with slots at the top of the
mounting plate. Hold the device at about 45° to the mounting
plate to align the tabs with the slots.
– Slide the device's tabs into slots so the device can pivot.
– Carefully rotate the device into place against the mounting
plate while checking the clearance between wires and the
back of the device. If wires are routed as described in Step 2,
the product will rotate against the mounting place without
force.
– The device should be seated flush on the mounting plate.
– Fasten the product-mounting screw on the front of the device
by hand-tightening. Stop when it is secure.
Note: Over-tightening may strip the screw connection. If the
screw cannot be fully tightened, check the wiring to make sure it
is not interfering with the product. (See Figures 3 and 4.) If the
screw strips the mounting plate, discontinue use of this product
and replace with a new product.
Note: If there is a cosmetic gap between the product and the ceil-
ing, the back box can be adjusted to be flush or slightly recessed
with the ceiling and the wires dressed to not interfere with the
back of the product. (See Step 1 and Step 2.)
System Sensor
®
is a registered trademark of Honeywell International, Inc.
Screw
FIGURE 6. ATTACHING DEVICE (CEILING VERSION SHOWN)
5. PERFORM REQUIRED SYSTEM TESTS.
In accordance with NFPA 72 standards, the system should be
100% functionally tested prior to use.
2
A0536-01
Product-mounting Screw
E56-6556-003
©2018 System Sensor. 11/29/2018
A0537-01

Publicidad

loading