IS 3180 (Fig� 5�10)
Mounting
20 m lens
height
Setting level tangential
1.5 m
8
5 m
–
6 m
–
7 m
–
8 m
20
12 m
2.0 m
8
5 m
–
6 m
–
7 m
–
10 m
20
20 m
2.5 m
8
6 m
–
8 m
–
10 m
–
13 m
20
20 m
3.0 m
8
8 m
–
9 m
–
12 m
–
17 m
20
20 m
Note:
The factory setting is 20 m
• Fit sensor and load module together and screw into place.
• Switch ON power supply�
• Set functions. (➔ "6� Function")
• Fit designer trim.
6� Function / operation
Factory settings
Twilight level: 1000 lux
Time setting: 5 s
Twilight setting (Fig� 6�1)
The chosen sensor response threshold is infinitely adjustable from approx. 2-1000 lux.
Control dial
means twilight mode at approx. 2 lux.
Control dial
means daylight operation / independent of ambient light level.
Teach mode
The control must be set to
at the level of light at which you want the sensor to
respond to movement from now on. The level of ambient brightness measured in this
way will be saved after 10 seconds. The load is deactivated during this period.
8 m lens
radial
Setting level tangential
2.5 m
4
3 m
2.0 m
2.5 m
–
5 m
2.5 m
3.0 m
–
6 m
3.0 m
3.0 m
–
7 m
3.0 m
4.5 m
8
9 m
3.5 m
2.5 m
4
4 m
3.0 m
3.0 m
–
5 m
3.0 m
3.5 m
–
6 m
3.0 m
4.0 m
–
8 m
3.0 m
4.5 m
8
8 m
3.5 m
3.0 m
4
5 m
3.0 m
4.0 m
–
7 m
3.5 m
5.0 m
–
8 m
3.5 m
5.0 m
–
9 m
4.0 m
4.0 m
8
10 m
3.5 m
4.0 m
4
5 m
3.0 m
4.5 m
–
6 m
3.0 m
5.0 m
–
8 m
4.0 m
4.0 m
–
10 m
4.5 m
4.0 m
8
13 m
5.5 m
30
Dazzle guard
This product is equipped with an integrated dazzle guard. If blinded by extraneous
light, this puts the sensor into a brightness-related evaluation mode for 60 seconds.
radial
(➔ "12� Troubleshooting")
Presence detector switch-off logic
The load connected is switched OFF once the selected light level is exceeded.
Time setting (Fig� 6�1)
The time you want the connected lamp to stay ON for is infinitely adjustable from
approx. 5 seconds of a maximum of 15 minutes. Any movement detected before this
time elapses will restart the timer.
Pulse function
The pulse function activates the output for 2 seconds (e.g. for staircase lighting time
switches). The sensor will then be in a dead time for 8 seconds.
Note:
If the pulse function is selected via the controller, time cannot be set via remote
control.
Manual override function (Fig� 4�1)
If a mains switch is installed in the mains supply lead, the following functions are
available in addition to simply switching ON and OFF:
Important: The switch should be actuated in rapid succession (in the 0.5 - 1 s range).
Sensor mode
1) Switch light ON (when light is OFF): switch ON and OFF once.
Sensor stays ON for the period selected.
2) Switch light OFF (when light is ON): switch ON and OFF once.
Sensor goes out or switches to sensor mode.
Manual override
1) Activate manual override:
Switch ON and OFF twice. The sensor is set to stay ON for 4 hours (red LED lights
up behind the lens). Then it returns automatically to sensor mode (red LED OFF).
2) Deactivate manual override:
Switch ON and OFF once. Sensor goes out or switches to sensor mode.
LED function
– Normal mode: LED stays OFF
– Test mode: LED lights up on detecting movement
– Remote control: LED flashes approx. 10 times per second
– Permanently ON/OFF: LED lit
31