lancer XBT-L1000 Manual De Instrucciones página 13

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

6 - Parameters of the Modbus Plus protocol
6.1 For the XBTs
- Select the connection points of the agent XBT of the Modbus Plus network. Under XBT-
L1000, from the configuration menu, select protocol parameters.
6.2 For the TXBTs
- The configuration of the address in XBT-L1000 is ignored.
7 - Objects supported / Syntax
Kind of supported
object
internal word bit
internal bit et output
bit
input bit
input register
Word, double word,
floating, chain
Mnemonic identifiers
8 - Implementation
8.1 For the XBTs
The Modbus Plus PCMCIA card TSXMBP100
Refer to the documentation on the TSX MBP100 card
The user must provide the following items (available from the Schneider Automation catalogue) :
• A tap-off cable, 2.4 to 6 m long :
W9 152 6284 0111 A 04
Mnemonic
(Syntax)
400001 + i, j
00001 + i
10000 + i
30000 + i
400001 + i
i : (0...65535)
j : BYTE (0...0x0F
13
Modbus Plus protocol
E
N
G
L
I
S
H
09 - 1999

Publicidad

Tabla de contenido
loading

Tabla de contenido