ZIV P+C 1CPX Manual De Instrucciones página 314

Unidad central de subestación
Tabla de contenido

Publicidad

El fichero para RTUs del tipo SEPAM queda de la forma:
[1]
# Configuracionde MODBUSMS
[2]
# SUBESTACION ACTUR
[3]
# Configuracion de MODBUSMS
[4]
# Parametros de comunicaciones del port
[5]
COM3,19200,I,8,1,
[6]
# TimeRTSon(ms),timeRTSoff(ms),ToutRX(ms),NumReintentos,NivelMonitor,
[7]
# NOTA: Para los modulos T-MOD no hay que usar el RTS
[8]
0,0,66,3,0,
[9]
# TimeExpMedidas(seg),TimeExpCont(seg),TimePulso(seg),TimeExpGenerico(seg),
TimeExpSincro(seg),
[10]
# TimeEsperaTrasReset(seg), ToutSincroBroadcast(mseg),
[11]
20,0,50,0,25,60,22,
[12]
# Direccion (PROCOME) del primer equipo logico equivalente
[13]
32,
[14]
# NumRTUs(Max 25),TipoDeRTUs(T-DAM(0),GENERICO(1),MICOM(2),SEPAM(3)),
[15]
1,3,
[16]
#
[17]
# SEPAM S81:
[18]
#====================================================================
[19]
#------- EQUIPO LOGICO 1: ACTUR - BARRAS 1 10KV (tipo BARRAS MT, B-MTC2-SZ)
[20]
#====================================================================
[21]
#Dir,TotISCs,ISCMasAlta,TotISE,ISEMasAlta,TotISS,ISSMasAlta,TotMea,TotCon,DirLoca
l,ISCLocal,ISCFallo
[22]
1, 22,21, 10,9, 0,0, 4, 0, 256,493, 86,
[23]
# DirLocal= Dir.(PROCOME) primer equipo logico equivalente + DirRTU = 33
[24]
##
[25]
# Numero de ISCs
[26]
22,
[27]
# ISC,alarma,f.activa,f.desact,flanco alrm,bocina,
[28]
0,0,1,1,0,0,
[29]
1,0,1,1,0,0,
[30]
2,0,0,0,0,0,
[31]
3,0,0,0,0,0,
[32]
4,0,1,1,0,0,
[33]
5,0,1,1,0,0,
[34]
6,0,1,1,0,0,
[35]
7,0,1,1,0,0,
[36]
8,0,1,1,0,0,
[37]
9,0,1,1,0,0,
[38]
10,0,1,1,0,0,
[39]
11,0,1,1,0,0,
[40]
12,0,0,0,0,0,
[41]
13,0,0,0,0,0,
[42]
14,0,0,0,0,0,
[43]
15,0,0,0,0,0,
[44]
16,1,0,0,0,0,
[45]
17,1,0,0,0,0,
[46]
18,1,0,0,0,0,
[47]
19,1,0,0,0,0,
[48]
20,0,0,0,0,0,
[49]
21,0,0,0,0,0,
[50]
##
[51]
# Numero de ISEs
[52]
10,
[53]
# ISE,DirEqEst,ISCEst,Time,Negada,DirEqOK,IscOK,DirEqBAD,IscBAD,doble,
n blqs,dir,isc,neg,..,
[54]
# DirEq=DirLocal=32+1
© ZIV Aplicaciones y Tecnología, S. A. Zamudio, 2004
configuración de los emuladores de protocolo
//
RESERVA 0 (Ox C100)
//
RESERVA 1 (Ox C101)
//
RESERVA 2 (Ox C102)
//
RESERVA 3 (Ox C103)
//
SECCIONADOR B1 POSICION CERRADO
//
SECCIONADOR B1 POSICION ABIERTO
//
RESERVA 6 (Ox C106)
//
RESERVA 7 (Ox C107)
//
RESERVA 8 (Ox C108)
//
SECCIONADOR PAT POSICION CERRADO
//
SECCIONADOR PAT POSICION ABIERTO
//
RESERVA 11 (Ox C10B)
//
CONTROL SIN MANDO
//
CONTROL MANDO LOCAL
//
RESERVA 14 (Ox C10E)
//
RESERVA 15 (Ox C10F)
//
UCP/S MAGNETO/S CC ABIERTO
//
UCP/S FALTA CC O FALLO
//
UCP FALLA CC SUPERVISION
//
MAGNETO TENSIONES HOMOPOLARES
//
RESERVA 20 (Ox C114)
//
RESERVA 21 (Ox C115)
B.8-11
LCPX403A

Hide quick links:

Publicidad

Tabla de contenido
loading

Productos relacionados para ZIV P+C 1CPX