CONTROLLED LOAD TYPE
◊ 230VAC halogen lamps: 35 - 300W
◊ 12V halogen lamps with electronic transformer: 35 - 300W
◊ Dimmable compact fluorescent lamps (CFL): 10 - 300W
◊ Dimmable 230VAC LED lamps: 10 - 200W
For each module, connect only lamps of the same type.
Power supply voltage
Consumption
Inputs
Indications
Positioning
Approvals
Operating temperature
Storage temperature
Relative air humidity
Weight
Dimensions
*
Use SCAME power supply unit ART. 100.20022101 or other limited power
source.
** With access allowed only for support or servicing by qualified personnel.
TECHNICAL CHARACTERISTICS
24VDC ± 5%*
15 to 25 mA
1 digital input can be used only for
connecting a button for controlling
the local dimmer, and not for the
presence detection sensor
1 LED (yellow) for indicating bus
status: when flashing, indicates
data transmission via bus, when
lit steadily indicates lack of power
supply negative or incorrect device
connection.
On a DIN rail on a dedicated control
panel or in junction boxes**
CE
0° to 40°C INDOOR USE
-10° to +70°C
5 to 95% with no condensation
70g
35x90x58 mm (2 DIN modules)
7