Contact-less direct and alternating
TRMS current transducer
Overall description
The T201DCH is an isolated, contact-less direct and alternating TRMS current transducer.
The device's function and look are very similar to those of an active standard CT, but with
the remarkable feature of measuring the continuous component of the pass-trough
current. For its electrical endurance, ease of use and compact dimensions,the T201DCH
fits every kind of current measurement up to 50 Adc or 50Aac.
Similar usage to a standard alternating current active CT.
HW
No shunt, no wasted power of primary current circuit.
High accuracy rating: class |0.5|.
Suitable for use with all the Seneca modules that supply the T201DCH
with at least 12Vdc and that have a 0-10Vdc analogue input
Two ranges that are dip-switch selectable.
Damping filter availability to improve stable reading.
Suitable for batteries , battery chargers, solar panels, power units and
generic dc loads.
Compact size: overall dimensions equal to
SENECA s.r.l.
Via Germania, 34 - 35127 - Z.I. CAMIN - PADOVA - ITALY
Tel. +39.049.8705355 - 8705359 - Fax +39.049.8706287
e-mail: info@seneca.it - www.seneca.it
This document is property of SENECA srl.Duplication and reproduction are forbidden,if not authorized.Contents of
the present documentation refers to products and technologies described in it. All technical data contained in the
document may be modified without prior notice. Content of this documentation is subject to periodical revision.
MI002441-E
Technical features
Limit values
0.. 50A DC/AC (polarity does not affect the measure)
Measure type
TRMS
Range
0-50 Arms or 0-25Arms, selectable by dip-switch
Peak factor
2
Pass-band
2.5 kHz
When a sheathed wire is used, the insulation voltage is set by
Insultation
sheath properties.
On a bare wire, it's stated 1 kV
Over-current
2000 A impulsive, 300 A permanent
OUTPUT AND POWER SUPPLY
0..10 Vdc, min load R
Type
common with the power supply. Screw terminals: Vout, GND
Terminals
Screw terminal pitch 5.08mm for max 2.5 mm
Hole diameter
12.3 mm
11.5..28 Vdc (between Vcc and GND)
Power supply
- P olarity reversal.
Protections
- Over-temperature.
21 mA (without load)
Current consumption
Accuracy rating
|0.5|
Precision class
- If the range is 50 A: 0.5% of end scale
(over the 2% of end
- If the range is 25 A: 1% of end scale
scale)
Precision class
- If the range is 50 A: 1% of end scale
(under the 2% of end
- If the range is 25 A: 2% of end scale
scale)
Resolution
12 bit (4000 points)
Temperature coefficient < 200 ppm/°C.
Error due to EMI
< 0.5%
- Fast filter: 800 ms.
Response time
- Slow filter: 2000 ms.
Measure hysteresis
0.15% of the end scale
MI002441-E
T201DCH
Key features
41 x 44 x 26 mm
ENGLISH - 1/4
INPUT
DC
=2 k . Output has the negative in
LOAD
2
ACCURACY
ENGLISH - 2/4
Protection index
Temperature
Storage Temperature
Humidity
Altitude
Weight
Overall dimensions
Box material
Standards
1 2
The symbol in the table above means switch in ON position; the T201DCH factory setting
is 50A, filter 800ms.
10
.
5
0
cables
The T201DCH can be located in any position and place, in accordance with the operating
conditions above stated. Use the included holder bracket when fixing to a DIN rail.
WARNING: High-strength static magnetic fields may change the output value: let avoid
closeness to permanent magnets, electromagnets or iron bulks that cause such a modifi-
cation of the surrounding magnetic field; try a different arrangement or orientation if zero-
error was greater than expected.
Multi-turn primary winding to improve sensibility
You can increase the sensibility of T201DCH simply passing several times in the hole with
the measuring current, realizing turns with multiplicative effect: for example, passing 5
times in the hole, as to see 4 turns, choosing a 50 A range, you get an equivalent sensi-
bility of 10 A full-scale. When you make this, let dispose the turns with symmetry in order
to preserve accuracy: use diametric contraposition with 2 turns, cross disposition with 4
turns, with 6 turns as like as 4 + 2, and so on.
Disposal of electrical & electronic equipment (applicable throughout the EU and other countries wit separate collection programs). This symbol, found on your product or on
its packaging, indicates that this product should not be treated as household waste when you wish to dispose of it.Instead,it should be handed over to an applicable collection
point for the recycling of electrical and electronic equipment. By ensuring this product is disposed of correctly, you will help prevent potential negative consequences to the
environment and human health, which could otherwise be caused by inappropriate disposal of it. The recycling of materials will help to conserve natural resources. For more
detailed information about the recycling of this product, please contact your local city office, waste disposal service or the retail store where you purchased this product.
OPERATING CONDITION
IP20.
-10..+65 °C.
-40..+85 °C.
10..90 % non-condensing.
Up to 2000 m a.s.l.
CASE
47 g.
41 x 44 x 26 mm (without terminals).
PBT, black
STANDARDS
EN61000-6-4/2007-01 (electromagnetic emission, industry).
EN64000-6-2/2006-10 (electromagnetic immunity, industry).
EN61010-1/2001 (safety).
DIP-switches
Range
1
0.. 50A
0.. 25A
±25
Input (A)
MI002441-E
+
+
V
V
T201DCH
T201DCH
SENECA
SENECA
AC/DC TRMS current
AC/DC TRMS current
transducer
transducer
50 A
50 A
0.5
0.5
25
25
50
50
ET003840
ET003840
Off
Off
Mounting
MI002441-E
Filter
2
Filter 10%-90% =800ms
Filter 10%-90% =2000ms
±50
ENGLISH - 3/4
+
+
P.S.
11.5..28 Vdc
P.S.=power supply
V= 0.. 10 Vdc output
N.c.=not connected