Technical Data - Appendix
Display and operating
level
Certification
Appendix
34
Terminal connections
Power supply and current output
Sensor connection
Remote operation
Configuration set
PC configuration kit
Configuration
Using PC programme
Interface
PC interface connection cable TTL -/- RS 232 with plug
Sensor type and connection type, engineering units (°C/°F), measurement range,
internal/external cold junction compensation, cable resistance compensation on
Configurable
2 wire connection, fault conditioning, output signal (4...20/20...4 mA), digital filter
parameters
(damping), offset, measurement point identification (8 characters), output
simulation
The measurement system fulfills the requirements demanded by the EU
CE mark
regulations. The manufacturer acknowledges successful unit testing by adding
the CE mark.
For further details on the available Ex versions (ATEX, FM,CSA, etc.) contact
your respective sales organisation. All relevant data for hazardous areas can be
Ex certification
found in separate Ex documentation. If required, please request copies from
your sales organisation.
12 Appendix
Short form instructions (SETUP)
Presettable parameters
Standard settings
(Quick-SETUP)
Expanded settings
Service functions
[1] 2-, 3-, or 4-wire connection
[2] on TC-connection
[3] on 2-wire connection
2-wire
- Sensor type (see Chap. 11 Techn. data)
[1]
- Connection mode
- Units (°C/°F)
- Measurement range start (see Chap. 11 Techn. Data)
- Measurement range end (see Chap. 11 Techn. Data)
- Cold junction compensation (internal/external)
- Compensation resistance (0...20 Ω)
- Fault condition reaction (see Chap. 11 Techn. Data)
- Output (analogue standard/inverse)
- Damping (0...60 s)
- Offset (-9.9 to +9.9 K)
- Measurement point indentification/TAG
- Simulation (on/off)
SETUP socket
3-wire
4-wire
[2]
[3]