Note: to properly check the static load alarm threshold, the load has to be applied
constantly for at least 5 seconds.
VERIFY ABSENCE OF ALARMS
To complete the checks, make sure that the sensor detects no alarms from vibrations
or changes in the slope that might be caused by the awning's structure when moving.
If the end bar vibrates notably when opening or closing, or if the support arm permits the
awning to slope downward beyond the static load threshold, the sensor could detect an
unwanted alarm condition.
Close the awning completely and wait at least 15 seconds. Give the open command and
verify that the awning opens completely.
If the awning stops and closes back up again, one of these causes might be responsible:
- excessive vibrations on the end bar: in this case, increase the vibration detection
threshold
- support arm slope: if possible,increase the static load alarm threshold. If the awning's
structure is not appropriate, then this function must be disabled permanently.
To change the thresholds set, unsnap the shell, deactivate the sensor and then
reactivate it.
ATTENTION!!! To avoid any hazardous situations, before unsnapping the shell,
see the proper procedure in the section: "DISABLE THE SENSOR".
22