No: 24056 – 08/18 rev. 2
Catalog Number • Numéro de Catalogue • Número de Catálogo: LMFC-011
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
This unit is pre-set for Plug n' Go™ operation, adjustment
is optional.
For full operational details, adjustment and more features of the product,
see the DLM System Installation Guide provided with Wattstopper room
controllers, and also available at www.legrand.us/wattstopper.
Installation shall be in accordance with all applicable regulations,
local and NEC codes. Wire connections shall be rated suitable for the
wire size (lead and building wiring) employed.
Installation shall be in accordance with all applicable regulations, local
and NEC codes. Fixture assembly, UL Listing compliance, and Class 1
/ Class 2 wiring separation best practices are the responsibility of the
fixture OEM and/or installing contractor.
PLACEMENT EXAMPLE
Daylighting
Sensor
LMFC-011
Installed in
a fixture
The LMFC-011 communicates with all other DLM
devices connected to the DLM Local Network.
Connections shown are for example only. The low
voltage LMRJ cables can connect to any DLM
device with an open RJ45 receptacle.
#18AWG solid copper wire is required for line
voltage wiring. Each relay is rated for up to 3A; total
load for LMFC-011 not to exceed 3A. Specified load
types can connect to any load relay. Do not connect
different load types to the same relay.
Large zones of fixtures with DLM capabilities are
created by connecting them to the LMZC-301 zone
controller and additional devices such as sensors
and switches. The total number of devices should
not exceed 47 for each Network (A & B), for a
maximum of 94 devices.
DLM Local Network
(low voltage, Class 2)
LMRJ cables
Corner Mount
Occupancy
Sensor
LMRJ-CS8
Coupler/Splitter
Ceiling Mount
Occupancy
Sensor
Wattstopper
DLM Single Relay w/0-10V Dimming Fixture Controller
DLM Relais simple avec contrôle de gradation 0-10 V
DLM Controlador de regulación de luminarias de un solo relé de 0 a 10 V
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
Voltage .......................................................................................... 24vDC
Relay Rating
Ballast, Tungsten, E-Ballast, CFL & LED ............... 3A@120V/277V
Ballast & LED ...................................................................3A@347V
Current Consumption ........................................................................ 7mA
Power Supply ................WattStopper Zone/Room/Plug Load Controllers
Connection to DLM Local Network ............. 1 or 2 RJ-45 ports per fixture
Class 2 dimming control signal:
0-10VDC, sinks up to 3mA for control of compatible ballasts
Environment:
Operating Temperature ........ 32° to 158°F (0° to 70°C) @120/277V
.................................................... 32° to 131°F (0° to 55°C) @347V
Storage Temperature .............................. 23° to 176°F (-5° to 80°C)
Relative Humidity ................................ 10 to 95% (non condensing)
LMZC-301
Zone
Controller
Switch/
Dimming
Switch
CONNECTIVITY
Ceiling Mount
OccupancySensor
LMRJ-CS8
Splitter
Switch
Dimming
Switch
Daylighting Sensor
Corner Mount
Occupancy Sensor
®
SPECIFICATIONS
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
CAUTION
TO CONNECT A COMPUTER TO THE DLM
LOCAL NETWORK USE THE LMCI-100. NEVER
CONNECT THE DLM LOCAL NETWORK TO AN
ETHERNET PORT—IT MAY DAMAGE COMPUTERS
AND OTHER CONNECTED EQUIPMENT.
DLM Local Network
Low Voltage
LMRJ Cables
LMZC-301
Zone
Controller
LMFC-011
Fixture Controller
Network A
Network B
LMRJ-CS8
Splitter

Publicidad

loading

Resumen de contenidos para LEGRAND Wattstopper LMFC-011

  • Página 1 For full operational details, adjustment and more features of the product, see the DLM System Installation Guide provided with Wattstopper room Class 2 dimming control signal: controllers, and also available at www.legrand.us/wattstopper. 0-10VDC, sinks up to 3mA for control of compatible ballasts Environment: Installation shall be in accordance with all applicable regulations, Operating Temperature ..
  • Página 2 MOUNTING AND WIRING Mount the LMFC-011 to the fixture. There are two DLM connector options for mounting to the fixture: The LMFC-RJ-50-24 provides a single RJ-45 port, and the LMFC-2RJ provides two RJ-45 ports. Use LMRJ cables to connect to other DLM devices. The LMFC-RJ-50-24 requires a hole in the fixture for a standard 1/2”...
  • Página 3 UNIT ADJUSTMENT - PUSH N’ LEARN (PNL) DLM Local Network – 24V (RED) BLUE DLM Local Network – GND (BLACK) DLM Local Network – COM (BLUE) Load Selection Procedure LOAD Blue LED ON when A configuration button (Config) allows access to WattStopper’s load is ON.
  • Página 4 Ballast, tungstène, ballast électronique, LFC et LED 3 A à 120 V/277 V du système DLM fourni avec Wattstopper contrôleurs de pièce et aussi Ballast et LED ..............3 A à 347 V disponible au www.legrand.us/wattstopper. Consommation de courant ............... 7 mA Alimentation électrique ......Zone WattStopper/Ambiance/ L'installation doit être effectuée conformément à...
  • Página 5 MONTAGE ET CÂBLAGE Montez le LMFC-011 sur le luminaire. Il y a deux options possibles afin d’installer les connecteurs aux luminaires: Le LMFC-RJ-50-24 fournit un port RJ-45, et le LMFC-2RJ fournit deux ports RJ-45, Utilisez les câbles LMRJ pour se connecter à d’autres composantes DLM. Le LMFC-RJ-50-24 requiert une ouverture dans le luminaire soit la dimension standard d’un connecteur ½”é.
  • Página 6 FONCTIONNEMENT EN PLUG n' GO (PnG) Pour plus de détails concernant l'utilisation du PnG et sa liaison à plusieurs unités, consultez les instructions d'utilisation du LMZC-301. Arbitrage de régulation de charge Pour profiter au maximum des avantages de la configuration PnG automatique, respectez ces simples règles d'arbitrage de régulation de charge.
  • Página 7: Especificaciones

    Balasto, tungsteno, balasto electrónico, CFL y LED 3 A@120 V/277 V proporciona con el controlador de habitación Wattstopper; también está Balasto y LED ..............3 A@347 V disponible en www.legrand.us/wattstopper. Consumo de corriente ..............7 mA Suministro de energía ......Controladores de carga de zona/ La instalación debe realizarse conforme con todas las...
  • Página 8 MONTAJE Y CABLEADO Montaje del LMFC-011 al luminaria. Hay dos opciones de conectores DLM: Modelo LMFC-RJ-50-24 tiene un solo puerto de RJ45 mientras que el modelo LMFC-2RJ tiene dos puertos. Use cables LMRJ para realizar conexiones entre productos. LMFC-RJ-50-24 requiere un agujero de medida típica de conectores de 1/2”. Monte el conector a la fixtura asegurándolo con la tuerca. Para el LMFC-2RJ , utilice el diagrama con las mediciones del agujero.
  • Página 9 FUNCIONAMIENTO DE PLUG n’ GO (PnG) Para ver una explicación detallada del funcionamiento de PnG y la secuenciación con varias unidades, consulte las instrucciones de instalación del LMZC-301. Arbitraje de control de carga Para aprovechar completamente la configuración automática de PnG, revise estas reglas simples acerca del arbitraje de control de carga. Después de conectar los controladores de la habitación a la red local DLM y de encenderlos, automáticamente negociarán para determinar cuál controlador será...
  • Página 12 No. 24056 – 08/18 rev. 2 © Copyright 2018 Legrand All Rights Reserved. 800.879.8585 © Copyright 2018 Tous droits réservés Legrand. www.legrand.us/wattstopper © Copyright 2018 Legrand Todos los derechos reservados.