Power supply
Current consumption from power supply with a rated
voltage of 24 V DC
-
Starting current
-
In standby
-
With alarm, device variants FCS-320-TM and
FCS-320-TM-R
Max. wire gauge
Housing material
Housing color
Protection category according to EN 60529
-
Without air return
-
With pipe section 100 mm/pipe bend
-
With air return
Permissible temperature range
-
FCS-320-TM series Aspirating Smoke Detector
-
Pipe system PVC
-
Pipe system ABS
Permissible relative humidity (non-condensing)
Sound power level (at 9 V fan voltage)
Response sensitivity (light obscuration)
Life cycle of fan (at 12 V and 24 °C)
F.01U.123.590 | 1.0 | 2009.11
15 V DC-30 V DC
Fan voltage
9 V
10.5 V
150 mA
105 mA
125 mA
110 mA
130 mA
2.5 mm²
Plastic (ABS)
Papyrus white (RAL 9018)
IP 20
IP 42
IP 54
-20 °C to +60 °C
-10 °C to +60 °C
-40 °C to +80 °C
Max. 95%
40 dB(A)
0.5 to 2.0%/m
60,000 hrs
FCS-320-TM | FCS-320-TM-R
12 V
13.5 V
145 mA
170 mA
150 mA
175 mA
Bosch Sicherheitssysteme GmbH