Remote control
(CN591) mode switch
SW 500
Functions
Operating
Details
Do not use the CN591
remote
control
ON/OFF
Prohibited/Allowed
mode
1
ON/OFF
Prohibited/Allowed mode 2
(level input)
ON/OFF
Prohibited/Allowed mode 3
(pulse input)
Coin timer mode 1 (for a no-voltage
contact point a)
Coin timer mode 2 (for a no-voltage
contact point b)
Cooling-H eating/Temperature settings
mode 1 (3 temperature patterns)
Cooling-Heating/Temperature settings
mode 2 (8 temperature patterns)
No.
Manual operations prohibited when CN591 No. 1 and No. 3 are closed, permitted
when open.
Only when No. 1 and No. 3 are closed and manual operations are prohibited.
On when CN591 No. 1 and No. 2 are closed, off when open.
(Cannot be operated from the remote control when manual operations are pro-
hibited. Only valid when operated from the CN591 .)
On when CN591 No. 1 and No. 2 are closed, off when open.
Manual operations prohibited when No. 1 and No. 3 are closed, permitted when
open.
(Cannot be operated from the remote control when manual operations are pro-
hibited. Only valid when operated from the CN591 .)
On when CN591 No. 1 and No. 2 are closed, offwhen No. 1 and No. 3 are closed.
Manual operations prohibited when No. 1 and No. 4 are closed, and permitted
when No. 1 and No. 5 are closed.
Same as when they are open.)
Permitted and on when CN591 No. 1 and No. 2 are closed, manual operations
_rohibited and off when open.
(When permitted, the unit can be operated from the remote control.)
Manual operations prohibited and off when CN591 No. 1 and No. 2 are closed,
_ermitted and on when open.
(When permitted, the unit can be operated from the remote control.)
On when CN591 No. 1 and No. 2 are closed, off when open.
When No. 1 and No. 3 are closed
20 °C
When No. 1 and No. 4 are closed
24 °C
When No. 1 and No. 5 are closed
28 °C
(When multiple switches No. 3, 4, and 5 are closed, the highest temperature will
be selected.)
Heat when No. 1 and No. 6 are closed, cool when open.
Remote control operations are valid as always.)
On when CN591 No. 1 and No. 2 are closed, off when open.
1 and No. 3
No. 4
No. 5
Temperature settings
Open
Open
Open
16 °C
Closed
Open
Open
18 °C
Open
Closed
Open
20 °C
Closed
Closed
Open
22 °C
Open
Open
Closed
24 °C
Closed
Open
Closed
26 °C
Open
Closed
Closed
28 °C
Closed
Closed
Closed
30 °C
Heat when No. 1 and No. 6 are closed, cool when open.
Remote control operations are valid as always.)