EARTHING AND SHORT-CIRCUIT EQUIPMENT FOR HIGHT VOLTAGE OVERHEAD
LINES ACCORDING TO UNE-EN 61230
COMPOSITION
3 TML aluminium alloy clamps with screw tighten for cylindrical conductors with diameter between 10 and 70 mm.
3 copper cables with PVC insulation. Section and length depending on model.
3 TT-50 milling earthing lathe.
3 nylon bags to store and transport the equipment.
Composition according to customer specification. (See Annex)
CHARACTERISTICS
Short-circuit current "Icc": See table.
Temperature range: -25°C a 55°C.
INSTRUCTIONS FOR USE
1. Find the closest earthing point and secure the earthing G-clamp to it.
2. Place the clamp on the conductor and fix it using the appropriate pole.
3. Place the others clamps in the same way.
4. To uninstall the equipment, proceed in the reverse order.
5. Store the equipment in its bag.
MANTENANCE AND CONSERVATION
Storage:
In order to maintain its ability to protect workers, earthing and short-circuit equipment must be mantained and
stored in good conditions by user.
Check before use:
For safety equipment grounding must be subjected to a thorough visual inspection before use. Visible damage of
clamps, fittings, wire insulation or exposure of bare wire are considered major defects and the equipment should
be put out of use.
Before use must inspect the contact surface parts and the contact of the connection points should be brushed to
remove any remaining tank to obtain a good electrical contact for traffic flows or short-circuit currents.
Periodic inspection and testing service:
The equipment must be inspected every 3 years, verifying that there are no visible damage tweezers, or cable
connections.
If there is any doubt about the excellent condition of the device or equipment, should be removed.