Re g i ste r d es c ript io n
Digital output setup according to the mode:
• Alarm (AL): Threshold referred to the set parameter
• Pulse (PULS): Pulse weight numerical value
Digital output setup according to the mode:
• Alarm (AL): Hysteresis value
• Pulse (PULS): Pulse value format
ETHERNET set default
Restore the ETHERNET settings to the default values
(IP, account username&password)
Number of the stored AVG or MIN/AVG/MAX recordings
(according to the instrument model)
Timestamp of the first AVG or MIN/AVG/MAX recording
(according to the instrument model)
Timestamp of the last AVG or MIN/AVG/MAX recording
(according to the instrument model)
Status of AVG or MIN/AVG/MAX recording (according to
the instrument model)
Mode of AVG or MIN/AVG/MAX recording (according to the
instrument model)
Rate of AVG or MIN/AVG/MAX recording (according to the
instrument model)
Reserved
MIN/AVG/MAX recording parameter for position 1
MIN/AVG/MAX recording parameter for position 2
Available only for instrument with RS485 port.
Available only for instrument with ETHERNET port.
72
INTE G E R
F. code
Register
(Hex)
Words
(Hex)
03 / 04 / 10
2050
4
03 / 04 / 10
2054
2
10
2074
2
03 / 04
2100
2
03 / 04
2102
2
03 / 04
2104
2
03 / 04
2106
2
03 / 04 / 10
2108
2
03 / 04 / 10
210A
2
03 / 04 / 10
210C
6
03 / 04 / 10
2112
2
03 / 04 / 10
2114
2
P ro gr a mmabl e dat a
In Alarm mode:
$0001... full scale value of the set
parameter. The measuring unit changes
according to the set parameter. The
value is always expressed with the milli
(m) coefficient:
e.g. $38270=230000mV=230V
For Phase sequence parameter, set $0000.
In Pulse mode:
$0001...$270F (1...9999)
In Alarm mode:
$00...$32 (0...50%)
For Phase sequence parameter, set $00.
In Pulse mode:
$01=X.XXX kWh, VAh, varh / pulse
$02=XX.XX kWh, VAh, varh / pulse
$03=XXX.X kWh, VAh, varh / pulse
$04=X.XXX MWh, VAh, varh / pulse
$05=XX.XX MWh, VAh, varh / pulse
$06=XXX.X MWh, VAh, varh / pulse
$07=XXXX MWh, VAh, varh / pulse
$AAAA$AAAA=ETHERNET set default
e.g. $007F=127 recordings
UnixTime format. Convert the read
hexadecimal value in decimal format.
e.g. $522E$5FD4=1378770900
>09/09/13, 23:55:00
UnixTime format. Convert the read
hexadecimal value in decimal format.
e.g. $522E$5FD4=1378770900
>09/09/13, 23:55:00
Bit encoding:
b1(LSb)=status (0=stopped, 1=active)
b2=memory full (0=no, 1=yes)
b3=memory overwritten (0=no, 1=yes)
e.g. $0000$0002=010
>recording stopped, memory full
and no memory overwritten
$01=fill, $02=ring
BASIC instrument version:
$00=disabled
$01=01 minute
$05=05 minutes
$0A=10 minutes
$0F=15 minutes
$1E=30 minutes
$2D=45 minutes
$3C=60 minutes
ENH instrument version:
$0000=disabled
$0001...$0E10 (1...3600 s, with 10 s step)
Refer to the "Parameter codes" table
Refer to the "Parameter codes" table
MODBUS RTU/ASCII, TCP