Description
The T-200 Transition™ Series card reader is a card serial
number reader compatible with the following 13.56 mHz
technologies:
Vicinity (ISO 15693)
HID iCLASS
Infineon my-d
Philips I-Code Serial Number
Proximity (ISO14443)
DESFire
MIFARE
Mounting the reader
1. Find a suitable mounting position on the door frame
or wall.
2. Drill two vertical mounting holes 2.25" (57.2 mm)
apart on the mounting surface of the door frame or
wall.
Figure 1. Dimensions
1.75
[44.5mm]
4.20
[106.7mm]
front view
3. Drill one 1.00" (25.4 mm) diameter hole in wall for the
pigtail wire connection.
4. Follow the Cable Connection Chart to connect the
reader to the field panel and external door
equipment.
5. Mount the base plate to the wall using the supplied
screws.
®
Serial Number
®
Serial Number
®
Serial Number
®
Serial Number
1.0
[25.4mm]
side view
Transition Series
T-200 Model Reader (en-US)
6. Hook the top of the reader case to the top of the base
plate and press into place.
Figure 2. Aligning top cover, reader case, and base plate.
7. Install the supplied screw in the base of the reader.
8. Snap the cover on the top of the case.
Connecting the cable
1. The readers are supplied with a 8-conductor cable
pigtail with drain wire. Connect the pigtail to the host
panel. Use the Cable Connection Chart (below) to
correctly match the color of each wire.
Color
Black
Blue
Brown
Green
Orange
Red
White
Drain
2. Use a DC power source between 5-16 VDC.
3. Connect reader's drain wire to the cable shield.
Connect shield wires at the field panel.
Signal
Ground
Beeper
Red LED Control
Data 0
Green LED Control
5 to 16 VDC
Data 1
Shield Ground