Installation
2-7/8"
5 YEAR LIMITED
WARRANTY
Automatic Diagnostic Feature
The unique feature of the CEPC-1 is the ability to place the
unit in any location because the unit does not require an
accessible test switch. Instead, when the room switch is
turned OFF , the emergency luminaires stay ON for
2.5 seconds and indicate that an emergency power source
was available and that the CEPC-1, ballast and lamp(s) are
all functioning correctly.
This feature eliminates the need for manual monthly testing
and is approved for this purpose.
Troubleshooting & Maintenance of CEPC-1
When the normal room or area switch is ON, emergency
load and regular load fixtures should all be illuminated. If
CEPC-1 does not function properly on startup, perform the
following tests:
1.
To test normal operation, ensure branch circuit breaker
is connected and utility power is available. If green
LED is not illuminated, confirm wiring connections and
continuity to branch panels.
2.
To test emergency operation, ensure emergency
source is connected and red LED is illuminated.
Turn room switch to "OFF" position, and ensure that
emergency lights stay illuminated for at least
2.5 seconds. If emergency lights do not stay ON for
at least 2.5 seconds, confirm wiring connections and
perform testing on emergency panel and emergency
power source.
2
Emergency Power Control
2"
Recommended
Box Size
4-11/16
2"
1/2"
Single Gang
Plaster Ring
Plastic is UL 94-5VA
Flame Rated and Can
1-3/4"
be Mounted above the
Suspended Ceiling
EMERGENCY LIGHTING
EQUIPMENT 73PK
No maintenance is required to keep the CEPC-1 functional.
However, regular testing should be performed when the
lamps or ballasts have been replaced or when facility
remodeling has taken place.
Electrical Specifications
Model CEPC-1
120V or 277V Sensing Input
120V or 277V Load
20A Ballast Load Rating
1800W Incandescent Load Rating
@ 120V
1500W Incandescent Load Rating
@ 277V
UL 924 Listed
Mechanical Specifications
Mounts in 4-11/16" Junction Box
With Single gang plastic ring
UL 94-5VA Rating
Shipping Weight: 8oz.
Temperature: 32° F -140° F
(0° C – 60° C)
Color: White
Flush mounted size: 4-¾" x 2-¾" x ¼"
Body size: 2-7/8" x 1-¾"x 1-¾"