INSTALLATION
DEFINITIONS
Manual Mode of Operation
The pump is operated by manually adjusting the motor speed with the keypad. SVP1 and
SVP4 models.
Automatic Mode of Operation
The pump is paced by an external 4-20mA signal, LED light illuminate. SVP4 models only.
Increase Speed
Decrease Speed
MOUNT PUMP
Select a dry location (to avoid water intrusion and pump damage) above the
solution tank.
To prevent pump damage in the event of a pump tube leak, never mount the pump
vertically with the pump head up.
To avoid chemical damage from fumes, DO NOT mount pump directly over an open
solution tank. Keep tank covered.
Avoid flooded suction or pump mounted lower than the solution container. Draw
solution from the top of the tank. Pump can run dry without damage. If pump is
installed with a flooded suction, a shut-off valve or other device must be provided
to stop flow to pump during service.
DO NOT allow water intrusion into the motor or corrosion and damage will occur.
10
continued
4-20mA Mode Light
SVP Keypad
www.stenner.com
Output Percentage
Power
Prime