MEASURE, ACCURACY
Effective value of phase voltage and phase to phase voltage of the system (average)
Voltage
Measuring range: 20 – 500 Vrms phase to phase (290 Vrms phase to neutral)
Accuracy: ±0.5%
Effective value of current and system value average
Current
Measuring range: 0.02 – 5 Arms
Accuracy: ±0.5%
Displaying: 0.02 – 9.99 kA
Phase L1 frequency
Frequency
Measuring range: 40 – 500 Hz
Accuracy: ±0.5% ±1 digit
Phase and three phase active power system, phase and three phase reactive power, phase and three
Power
phase apparent power (addition)
Measuring range: 0.01 – 9990 kW, 0.01 – 9990 kVAr, 0.01 – 9990 kVA
Accuracy: ±1%
Phase and three phase power factor system (average)
Power Factor
Measuring range: -0.1 +0.1
Accuracy: ±1%
Temperature
Temperature sensed by internal sensor
Measuring range: 0 – 70ºC
Accuracy: ±2ºC (time delay to measure 15 minutes)
Active and reactive energy in the three phase system
Energy-meter
Measuring range: 0 – 99999999,9 kWh (kVArh)
Class 2 (IEC 1036)
POWER SUPPLY, INPUTS
Auxiliary supply
100-125 / 220-240 / 380-415 V (50-60 Hz)
Selfconsumption: 3 VA
Voltage input
From 20 to 500 V phase to phase
Continuous overload: +20%
Input impedance: 1MΩ
Connection on single phase, 3 or 4 wires system
Current input
From 0.02 to 5 A
Continuous overload: 30%
From external CT with secondary /5A, primary programmable from 5 to 10.000A (self consumption <0.5VA)
GENERAL SPECIFICATIONS
Display
4 displays with red LED composed by 3 digits of 8 segments
3 buttons to select measuring and programming of CT transformation ratio
Degree of protection: IP52 front, IP20 enclosure and terminals
Mechanicals
Weight: 0.5 kg
Maximum terminal section: 2.5 mm
Operational temperature: -10 +60ºC
Environment
Humidity: <90%
Stocking temperature –25 +80ºC
Insulation: 3 kV (1 min.)
Normatives and
CEI EN 50081-2, CEI EN 50082-1
Markings
CEI EN 61010-1
For each application and functional problems not treated in the present manual, it's possible to contact our technical assistance service.
The manufacturer declines any responsibility for eventual injury or damage to persons or things as result caused by misuse or improper use of
the instrument.
PAE Asuaran – Edif. Artxanda, 23
Tel. (94) 4711409 Inter. 34-94-4711409 - Fax. (94) 4710592 Inter. 34-94-4710592

TECHNICAL CHARACTERISTICS

±1 digit
±1 digit
±1 digit
±1 digit
2
CE
48650 ERANDIO - BIZKAIA
E-mail : fanox@fanox.com - http://www.fanox.com
ESPAÑA