MOUNTING
WARNING
Risk of injury or damage. Unit will fall if not installed
properly. Follow installation instructions.
A. ¾" Rigid Pendant Mount (Option 11):
Wet and Damp location Rated
1. Feed wires through ¾'' Rigid Pendant conduit and
thread pendant conduit into fixture top housing
(figure 1 - left).
2. Secure the conduit to the customer-provided water
proof junction box cover plate fittings.
3. Make necessary wire connections in the customer-
provided waterproof junction box (see figure 1- right).
4. Using customer-provided #10-24 x 0.5'' screws, fix
cover plate to the customer-provided junction box.
B. Surface mount with slide-on wiring box
(Option 20)
Wet and Damp location Rated
1. Remove accessory cover plate (see figure 2).
2. Using two customer-provided #10-24 x 0.5''
screws, fix mounting plate to the customer-provided
ceiling-mounted waterproof junction box, pulling
supply wiring thru the central opening.
3. Slide the fixture to the mounting accessory.
4. Make necessary wire connections in the
accessory wiring box.
5. Reattach the cover plate using the original screws.
(figure 3).
Surface Mount
Figure 2
Figure 1
Figure 3
C. Primary Electrical Disconnect (PED) Mounts
• PED with MPM-C (Option 1)
Damp location rated
• PED with MPM-3PR (Option 2)
Damp location rated
• PED with MPM-3PRW (Option 4)
Damp location rated
• PED with MPM-3PRTFW (Option 5)
Wet and Damp location rated
• PED with MPM-WW (Option 6)
Wet and Damp location rated
1. Remove accessory cover plate (see figure 4).
2. Attach hanging hardware to pendant conduit and
tighten screw, or attach junction box per local
electrical codes using customer-provided #10-24 x
0.5" screws.
3. Make necessary wire connections in upper portion
of mounting accessory.
MPM-C
MPM-3PRTFW
4. Slide the extrusion attached to the luminaire
completely onto the hanger extrusion and fully seat
the PED connector (see figure 5).
5. Reattach the cover plate using the original screws.
Figure 5
MPM-3PR
MPM-3PRW
MPM-WW
Figure 4
MPM-C
MPM-3PR
MPM-3PRW
MPM-3PRTFW
MPM-WW