Step 1
Clean pipe thoroughly in the area where the gaskets will seat.
For future use, place a reference mark on the pipe a minimum
of 3" from the end to insure that the coupling is properly cen-
tered over the opening between the pipe ends.
Note: On conducting type of compression couplings (pro-
tected gaskets) the pipe should be cleaned to bare metal to
insure electrical conductivity.
Step 2
Loosen compression nuts until gaskets are free.
Step 3
Lubricate gaskets and pipe ends with water, soap solution or
other suitable lubricant.
Step 4
Stab pipe ends into coupling, noting the reference mark for
proper centering on the pipe. Pipe ends must be a minimum
of 1/2" past the tip of the gasket to provide an adequate seal.
A gap of 1/4" between pipe ends is recommended.
Step 5
Tighten nuts sufficiently to prevent leakage. SEE TABLE for
recommended torque and wrench sizes. When tightening,
nuts must always be rotated. DO NOT ROTATE SLEEVE
while tightening the compression nuts.
Nominal Pipe
Size Inches
1/2"
3/4"
1"
1 1/4"
1 1/2"
2"
(ft. lbs.)
Water and Industrial
Foot
Pounds Torque
70
85
100
120
130
140
Torque
(wrench length in inches) (force on end of wrench)
=
Example: 140
ft. lbs.
Questions: Call 1-800-643-9705 or visit www.smith-blair.com
Installation Instructions
Type 525
Compression Coupling
Compression Nut
!
This product does not restrain
against axial pipe movement.
12
(24" wrench) (70 lbs)
=
12
Retainer
Gasket
Body
WARNING:
Wrench
Size
14"
18"
18"
24"
24"
24"
TI-013
1

Publicidad

loading

Resumen de contenidos para Xylem Smith-Blair 525

  • Página 1 PARA INSTRUCCIONES DE INSTALACIÓN EN ESPAÑOL, VEA LA PÁGINA 2. Water and Industrial TI-013 Installation Instructions Type 525 Compression Coupling Step 1 Retainer Clean pipe thoroughly in the area where the gaskets will seat. Gasket For future use, place a reference mark on the pipe a minimum Body of 3”...
  • Página 2 Agua y Drenaje TI-013 INSTRUCCIONES PARA SU INSTALACIÓN Tipo 525 Coples para compresión Paso 1 Retén Limpie la tubería perfectamente en el área den donde los empaques Empaque serán instalados. Como referencia ponga una marca en la tubería con una distancia mínima de 3 pulgadas del extremo con la finalidad Cuerpo de que el cople se encuentre centrado de manera correcta sobre la abertura entre los extremos de la tubería.