Descargar Imprimir esta página

Bosch FLM-420-I8R1-S Guia De Instalacion página 14

Ocultar thumbs Ver también para FLM-420-I8R1-S:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 16
14
en | Safety Notes
1
Safety Notes
Notice!
Installation must only be carried out by authorized specialist personnel.
Caution!
Electrostatic discharge (ESD)! Electronic components could become damaged.
Ground yourself using a wrist strap or take other suitable actions.
In order to comply with EN50130-4:2011, shielded cable is required for the installation. The
shielded cable needs to be applied for all loops and stubs which are equipped with one or
more modules and for all inputs which are connected. The cable shield wire for the LSN cable
has to be connected properly according LSN specifications.
2
Address settings
Fit a rotary switch in the required position using a pan head slotted screwdriver (1.4).
Address (A)
Operating mode
0 0 0
Loop/stub in LSN improved version mode with automatic addressing (T-taps not possible)
0 0 1 - 2 5 4
Loop/stub/T-taps in LSN improved version mode with manual addressing
CL 0 0
Loop/stub in LSN classic mode
3
Connection
Cables are fed through rubber bushings or PG cable glands (1.3). Connections, see (1.7):
Description
+U | 0V
LSN
a1- | b1+
LSN
Shield
+U | 0V
LSN
a2- | b2+
IN 1 - 8 + | -
REL
NC | COM | COM | NO
Notice!
The maximum cable length of all inputs connected to the loop or stub is 500 m in total.
Additionally, all outputs which are not electrically isolated from LSN must be included in the
total line length calculation (e.g. peripherals connected via C points).
The activation of the inputs IN 1 - 8 has to be carried out electrically isolated from LSN (e.g.
with relay contact, pushbutton, etc.).
The inputs must have a minimum activation time of 3.2 s.
2016.01 | 5.0 | F.01U.032.847
Function
Auxiliary power supply (support points to loop through)
LSN incoming
Cable shielding
Auxiliary power supply (support points to loop through)
LSN outgoing
Input 1 to Input 8
Change-over relay (NC contact/COM, COM/NO contact)
Installation Guide
Octo-input Interface Module with Relay
Bosch Sicherheitssysteme GmbH

Publicidad

loading