INSTALLATION INSTRUCTIONS, continued
2.
Insert the piggyback plug from the switches into a standard grounded outlet of proper voltage. For automatic operation plug the pump directly into the
piggyback plug. Pump can be manually operated by bypassing piggyback plug (see Figure 2).
NOTICE: For installation utilizing a watertight junction box or similar connections, see Figure 3.
NOTICE: For installation as a control switch for magnetic or combination starter, see Figure 4.
3.
Securely tape or clamp both piggyback switch cord and pump cord to the discharge pipe, clear of float operation (see Figure 1). Excess cord should be
coiled and fastened to the discharge pipe.
4.
Clean basin free of debris after installation.
Check and test your installation. Fill basin with water and allow pump to cycle to ensure proper range and operation. NOTICE: For installation utilizing a
5.
Piggyback Float Switch connection use Zoeller Qwik-Box. See FM1420.
FIGURE 2
AUTOMATIC
PUMP PLUG
OPERATION
SWITCH PLUG
A) Remove (cut) piggyback plug from variable level float switch. Remove approx. 3-1/2" (89 mm) of cord jacket and 1" (25 mm) insulation from wires.
B) Wire switch into circuit as shown.
C) Return to instructions.
D) Installation must be in agreement with the National Electric Code and all local codes.
ZOELLER SWITCH-MATE SINGLE PIGGYBACK VARIABLE LEVEL FLOAT SWITCH
REFER TO OTHER SIDE FOR INSTRUCTIONS FOR ALL APPLICATIONS.
10-0055 115 V/Max.
10-0032 115 V/Max.
10-0033 230 V/Max.
10-0034 115 V/Max.
10-0035 230 V/Max.
10-0063 115 V/Max.
10-0559 230 V/Max.
10-0705 115 V/Max.
10-0706 230 V/Max.
10-0748* 230 V/Max.
* no plug
Zoeller Switch-Mate Variable Level Float Switches are designed for use with the appropriate voltage and horsepower, nonautomatic, single phase, Zoeller pumps.
Maximum liquid temperature must not exceed 120 °F (49 °C) for 10-0748.
Zoeller Switch-Mate Variable Level Float Switches can be used as a control switch for a magnetic or combination starter. Maximum temperature must not exceed
140 °F (60 °C). See Figure 9.
Single Piggyback Variable Level Float Switches are recommended for use in 18" (457 mm) minimum diameter pits or basins.
NOTE: Consult factory for controlling units over 1-1/2 HP with variable level float switch.
FIGURE 3
MANUAL
OPERATION
SK308A
VARIABLE
SWITCHES
1/2 HP
13 A 10' (3 m) cord for EFFLUENT, SEWAGE and DEWATERING
1 HP
15 A
5' (5 m) cord for EFFLUENT, SEWAGE and DEWATERING
2 HP
15 A 15' (5 m) cord for EFFLUENT, SEWAGE and DEWATERING
1/2 HP
13 A 15' (5 m) cord for EFFLUENT, SEWAGE and DEWATERING
1 HP
13 A 15' (5 m) cord for EFFLUENT, SEWAGE and DEWATERING
1/2 HP
13 A 20' (6 m) cord for EFFLUENT, SEWAGE and DEWATERING
2 HP
15 A 20' (6 m) cord for EFFLUENT, SEWAGE and DEWATERING
3/4 HP
15 A 20' (6 m) cord for EFFLUENT, SEWAGE and DEWATERING
1 HP
13 A 20' (6 m) cord for EFFLUENT, SEWAGE and DEWATERING
3 HP
20 A 25' (8 m) cord for EFFLUENT, SEWAGE and DEWATERING
(120 °F [49 °C] maximum liquid temperature)